The Effect of Nozzle Collar on Single Phase and Boiling Heat Transfer by Planar Impinging Jet

평면 충돌제트에서 노즐 깃이 단상 및 비등 열전달에 미치는 영향

  • 신창환 (연세대학교 기계공학과 대학원) ;
  • 임성환 (연세대학교 기계공학과 대학원) ;
  • 우성제 (삼성전자 DA 사업부) ;
  • 조형희 (연세대학교 기계공학과)
  • Published : 2004.04.28

Abstract

The water jet impingement cooling is one of the techniques to remove heat from high heat flux equipments. We investigate the local heat transfer of the confined water impinging jet and the effect of nozzle collar to enhance the heat transfer in the free surface jet and submerged jet. Boiling is initiated from the furthest downstream and the wall temperature increase is reduced with developing boiling, forming the flat temperature distributions. The reduction in the nozzle-to-surface distance for $H/W{\leq}1$ causes the significant increases and distribution changes in heat transfer. Developed boiling reduces the differences in heat transfer for various conditions. The nozzle collar is employed at the nozzle exit. The distances from heated surface to guide plate, $H_c$ are 0.25W, 0.5W and 1.0W. The liquid film thickness is reduced and the velocity of wall jet increase as decreased spacing of collar to heated surface. Heat transfer is enhanced for region from the stagnation to $x/W{\sim}8$ in the free surface jet and to $x/W{\sim}5$ in the submerged jet. For nucleate boiling region of further downstream, the heat transfer by the nozzle collar is decreased in submerged jet compare with higher velocity condition. It is because the increased velocity by collar is de-accelerated at downstream.

Keywords