변형된 SOM을 이용한 유입변압기 열화진단

Diagnosis of Power Transformer Using Modified Self Organizing Map

  • 발행 : 2004.07.14

초록

Substation facilities have become large and complex in the electric power systems. Development of condition monitoring and diagnosis techniques have been very important to improve the security of substation transformers. This paper presents a method to analyze the cause and the degree of aging of power transformers by Self organizing map(SOM). Dissolved gas data were non-linearly transformed by sigmoid function to make determination of SOM close to that of human. Potential of a failure and the degree of aging of a normal transformer are identified by using the proposed quantitative criterion. Furthermore, transformer aging is monitored by the proposed criterion for a set of transformers. To demonstrate the validity of the proposed method, a case study is performed and its results are presented.

키워드