차단기 아크접점의 마모저감을 위한 차단시점제어
Control of the Breaking Instant for Mitigating Contact Wear of Circuit Breaker
- Lee W.Y. (Korea Electrotechnology Research Institute) ;
- Park K.Y. (Korea Electrotechnology Research Institute) ;
- Oh Y.H. (Korea Electrotechnology Research Institute) ;
- Chung J.K. (Korea Electrotechnology Research Institute) ;
- Kim H.J. (Vitzrotech Co.)
- 발행 : 2004.07.14
초록
The arcing contact wear of circuit breakers can be the major cause for the maintenance requirement. The control of arcing times as short as possible but larger than the given minimum arcing time may be the effective way to mitigate the contact wear and to lessen the expenditure of a maintenance. In this paper the method for minimizing the arcing time is described. The basic concept used in the proposed method is the estimation of the current interruption instant from the informations such as the phase angle at the instant of trip commands and the magnitude of interrupted currents.