Study on $H_2$ Sensing Characteristics of Gas Extractor for Dissolved Gas in Oil

유중 가스 검출장치의 수소 가스 감지 특성에 관한 연구

  • Published : 2004.07.05

Abstract

In oil-filled enuipment such as transformers, partial discharge or local overheating will precede a final shutdown. Accompanied with such problems is a decomposition of insulating material into gases, which are dissolved into the transformer oil. The gases dissolved in oil can be separated with some membranes based on the differences in permeability of membranes to different gases. This paper discuss the permeability characteristics of several membranes for separation hydrogen gas in oil. With result of this paper, it may become possible to detect fault-related gases from transformer oil and predict incipient failures in the future.

Keywords