Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference (한국전기전자재료학회:학술대회논문집)
- 2004.07b
- /
- Pages.1166-1170
- /
- 2004
Analyses of Leakage Current of Transmission Insulator as a Function of Environmental Condition
환경에 따른 송전용 애자의 누설전류 분석
- Choi, In-Hyuk (KEPRI) ;
- Lee, Dong-Il (KEPRI) ;
- Kim, Chan-Young (Woosuk Uni.)
- Published : 2004.07.05
Abstract
The leakage currents of transmission insulator were investigated as a function of environmental conditions, such as temperature, humidity, and rainfall. The insulators were artificially contaminated with insoluble yellow soil and kaolin which helped salt to stick on the surface of insulator. The insulators contaminated with the grade of B, C, and D were installed in the KoChang Testing Center. The leakage currents were measured and compared with non-contaminated insulators. The results indicated that the most important factor affecting leakage current was humidity. After heavy rain, the artificially contaminated salt was dissolved, resulting in similar characteristics between with and without contamination