UHF 부분방전 진단법에 의한 가스절연 개폐장치의 성능검증
Performance Verification of the Gas Insulated Switchgear using UHF Partial Discharge Diagnosis Method
- Kim, J.B. (Hyosung.co.) ;
- Jung, J.R. (Hyosung.co.) ;
- Kim, M.S. (Hyosung.co.) ;
- Song, W.P. (Hyosung.co.) ;
- Kim, M.H. (KERI) ;
- Ko, H.S. (Kyungnam National University) ;
- Choi, I.H. (KEPRI)
- 발행 : 2004.05.28
초록
In generally, compared with VHF band, electromagnetic waves of UHF band have a low influence for external noise. We can detect the real abnormality with several pC in GIS using UHF method. Recently, it has applied to use the external UHF sensor attached on spacer to GIS of existing substation. In this paper, we firstly described the technique of the partial discharge measurement using frequency analysis and phase analysis in UHF band. Secondly, we presented the results of sensitivity, the relationship of dBm-pC and diagnosis of the reason of PD source by phase analysis. And then, we report the diagnosis result of partial discharge on 800kV GIS in domestic substation. rge diagnosis of GIS.