The Measurement Error owing to Leakage of Gaugeline in Orifice Flowmeter

오리피스 유량계에서 게이지라인 누설에 의한 계량오차

  • 이철구 (한국가스공사 연구개발원) ;
  • 하영철 (한국가스공사 연구개발원) ;
  • 허재영 (한국가스공사 연구개발원)
  • Published : 2003.12.05

Abstract

This study was experimentally performed in order to estimate the errors due to the leakage of transmitter gaugelines in the orifice flow meter for natural gas. It would be a serious problem in safety if a large quantity of leak was occurred at the tubes or fittings like valve. But in most cases the safety problems might be rarely happened because the gas leak detectors could be operated in advance and the various kinds of inspection would be also fulfilled periodically. If the leakage was occurred continuously with an undetectable amount at the gaugelines for measuring the pressure or the differential pressure(DP), the amount of leakage might be an error or an unaccounted flow(UAE). In addition if the measuring value of pressure or DP were affected by the leakage, it might also be a measurement error. The experiments were performed to estimate the amount of leakage and to check the DP changes if it exited. First, through the measurement of the air pressure changes in the airtight container connected to a transmitter with gaugelines as the time passed, the amount of leakage causing from the fittings of gaugelines was roughly estimated. As changing the leak position of the gaugeline, the leak was intentionally made to break out. The variance of DP was checked as controlling the extent of leakage and compared to no leak conditions. Consequently, under the normal maintenance conditions, the result represented that the amount of leakage causing from the gaugelines was insignificant and also the DP changes on leakage conditions were too small to cause the errors of measurements.

Keywords