Abstract
Cooling load from the top plate to L$N_2$ surface, including wall conduction, gas conduction, radiation, and current leads, is investigated in a closed cooling system for HTS transformer. In general methods of load calculation, individual load is estimated separately, but they are actually coupled each other because of natural convection of nitrogen vapor. Using heat transfer analysis, we calculate cooling load with taking into account the effect of natural convection. Cooling load is under- estimated approximately 2 % when the natural convection is ignored. If the operating current is high, there will be a wide difference between actual cooling load and cooling load by individual calculation. Cooling load decreases with increasing number of radiation shield. With production, construction, and cooling load, three radiation shields are proper to 1 MVA HTS transformer.