Proceedings of the KIPE Conference (전력전자학회:학술대회논문집)
- 2003.07a
- /
- Pages.375-378
- /
- 2003
A study on the power factor improvement of Wind Turbine Generation System at Haeng-Won in Jeju
제주 행원 풍력 발전 시스템의 역률 개선에 관한 연구
- Park S.G. (Faculty of Electrical It Electronic Eng., Cheju Nat'1 University) ;
- Kim J.W. (Faculty of Electrical It Electronic Eng., Cheju Nat'1 University) ;
- Kang G.B. (Faculty of Electrical It Electronic Eng., Cheju Nat'1 University) ;
- Kim E.H. (Faculty of Electrical It Electronic Eng., Cheju Nat'1 University)
- Published : 2003.07.01
Abstract
This paper presents a study on the power factor improvement of the Wind turbine Generation System(WTGS) at Haeng-won wind farm in Jeju Island. Vestas WTGS named V47 as a model system is selected in this paper, and has 660 kW Power ratings. In this system, power factor correction is controlled by the conventional method with power condenor bank. So, model system at Haeng-won wind farm has very low power factor in the area of low wind speed, which is from 4 m/s to 6 m/s. This is caused by the power factor correction using power condenser bank To improve the power factor in the area of low wind speed, we used the static var compensator(SVC) using current controlled PWM power converter by IGBT switching device. finally, to verify the profosed method, the results of computer simulation using Psim program are presented to support the discussion.
Keywords