Correction of Overcurrent Protective Relay on Distribution Feeders Considering the Power Output of Wind Farm Interconnected with Utility Networks
계통 연계 풍력발전단지의 출력 조건을 고려한 배전선 과전류 계전기 정정
- Kim, J.W. (Kangwon National University) ;
- Jang, S.I. (Kangwon National University) ;
- Kim, K.H. (Kangwon National University) ;
- Yoo, N.S. (Kangwon National University) ;
- Park, H.J. (KEPRI) ;
- Song, D.S. (KEPRI) ;
- Lee, J.M. (KEPRI)
- 김지원 (강원대학교) ;
- 장성일 (강원대학교) ;
- 김광호 (강원대학교) ;
- 유능수 (강원대학교) ;
- 박현준 (한국전력 강릉지사) ;
- 송대선 (한국전력 강릉지사) ;
- 이재문 (한국전력 강릉지사)
- Published : 2003.07.21
Abstract
This paper describes the correction of overcurrent protective relaying set value in distribution networks interconnected with wind farm by dedicated line. The wind farm composed of wind turbine generators is one of the great energy sources; however, it would be also highly possible that the current in the point of common coupling is influenced by the output power of wind farm. So, the overcurrent relay applied in distribution feeders might generate trip signal for normal operation. In order to prevent the mal-operation of overcurrent relay, it is necessary to correct the relay's setting value according to the output power of end farm. This paper presents the influence of wind farm on the overcurrent relaying set value in distribution feeders for cases of fault as well as normal operation and proposes the basic strategy for correction of overcurrent relaying set value.