Test and Analysis of 3-D of Leakage Impedances in a Single-Phase 1MVA HTS Transformer

단상 1MVA 고온초전도 변압기의 누설임피던스 3차원 해석 및 시험

  • Published : 2003.07.21

Abstract

In this paper, 3-D nonlinear electromagnetic analysis of a single phase 1MVA 22.9 kV/6.6 kV high temperature superconducting(HTS) transformer with double pancake windings was accomplished. The characteristics of 1MVA HTS transformer such as The efficiency, voltage regulation and % impedance voltage drop were obtained by the 3-D non-linear electromagnetic analysis. And in order to verify the 3-D non-linear electromagnetic analysis of a single phase 1MVA HTS transformer, a 1MVA test transformer with windings made of copper tapes with the same size as BSCCO-2223 HTS tape was manufactured. The energy conservation method to perform the analysis of leakage impedances of both a 1MVA HTS transformer and test transformer was used. The characteristic analysis such as efficiency, voltage regulation and % impedance voltage drop of transformer was performed. And the obtained values of both 1MVA HTS transformer and test transformer were compared.

Keywords