A study on the PD detecting of C-GIS using AE sensor

AE센서를 이용한 C-GIS의 부분방전 검출에 관한 연구

  • Lee, H.Y. (LGIS ELECTROTECHNOLOGY R&D CENTER) ;
  • Lee, Y.H. (LGIS ELECTROTECHNOLOGY R&D CENTER) ;
  • Sin, Y.S. (LGIS ELECTROTECHNOLOGY R&D CENTER) ;
  • Seo, J.M. (LGIS ELECTROTECHNOLOGY R&D CENTER)
  • Published : 2003.07.21

Abstract

Recently, diagnostic techniques have been investigated to defect a partial discharge in high voltage electrical equipment. We have studied the characteristics of the acoustic partial discharge originating from the electrical defects in cubicle GIS(C-GIS). An acoustic emission(AE) sensor is used on the enclosure to detect partial discharge source because the sensor is sensitive to stress waves in its frequency range that may not be from a partial discharge source. AE signal is analyzed with phase-magnitude-frequency number(${\Phi}$-V-n) and pulse per second(PPS). Experience result has shown that the omitted acoustic signal has phase dependency and phase shift characteristic according to increase with applied voltage. These result will be helpful to the pattern recognition of the acoustic partial discharge in a C-GIS.

Keywords