A Nitrogen Permeability Experiment with the Various Thickness of Concrete

콘크리트 두께에 따른 질소투과계수 영향실험

  • Published : 2002.05.01

Abstract

Using the diffusion cell, a experimental study on the nitrogen permeability was performed with the various thickness of concrete. This is important with relating to the carbonation study because the study of $CO_2$ diffusivity needs to use thin concrete specimen. Experimental results show that the nitrogen permeability is few affected by concrete specimen's thickness. But, specimens with 1cm thickness have a high permeability and deviation relatively. Also, specimens with w/c ratio 0.40 have a low permeability than 0.58. Consequently, the 3cm thickness is the better stable than others but the 1cm thickness specimens will be stable in case having a lot of specimens.