모의 GIS 내부에 파티클 유입시 코팅전극의 절연파괴 특성

The Characteristic of breakdown Particle Contaminated Model GIS with Epoxy Coated Electrodes

  • 발행 : 2002.07.10

초록

One of the most frequent sources of the accident is metal contaminant in GIS. This paper deals with the characteristics of breakdown voltage of metallic particles using electrodes of various epoxy coating thickness. As experimental results, breakdown voltage of the thickly coated electrode is higher than that of thinly coated electrode. It is considered that resistance of the epoxy coating impedes the development of pre-discharges in the gas.

키워드