난연성 폴리 올레핀 케이블 절연재료의 내화특성

Fire Resistance Characteristics of Polyolefin cable Insulating Materials for Flame Retardant

  • 발행 : 2001.11.08

초록

In this paper, we analyzed the properties change of electric wire when the thermal stress was applied to NFR-8 and FR-PVC 600[V] wire. Messurement is made of the attenuation of a light beam by smoke accumulating with in a closed chamber due to nonflaming pyrolytic decomposition and flaming combustion. Results are expressed in terms of specific optical density which is derived from a geometrical factor and the measured optical density a measurement characteristic of the concentration of smoke. Referenced documents were ASTM E662 standard test method for specific Ds genalated by solid materials. The furnace control system shall maintain the required irradiance level under steady-state condition with the chamber door closed of $2.5{\pm}0.04[w/cm^{2}]$ for 20 min. According to the results of the smoke density analysis of NFR-8 and FR-PVC the highest decomposition flaming smoke density range of NFR-8 and FR-PVC were 25.2 to 37.5 and 51.1 respectively. Nonflaming smoke density range of NFR-8 and FR-PVC were 100.4 to 112.2 and 126.5 to 398.8. The amount of carbon monoxide generated was found to be much higher in FR-PVC decomposition than in NFR-8 due to incomplete combustion of FR-PVC which has high content of carbon in compound.

키워드