4도체 송전선로의 전력선 염회 분석 및 방지 방안

Analysis and Preventive Countermeasures of Power Line Twisting for 4-conductor bundle Transmission Line

  • 민병욱 (한국전력공사 대전전력관리처) ;
  • 안정식 (한국전력공사 대전전력관리처) ;
  • 남궁도 (한국전력공사 대전전력관리처) ;
  • 박재웅 (한밭대학교 전기공학과) ;
  • 김영달 (한밭대학교 전기공학과)
  • 발행 : 2001.11.16

초록

For 4-conductor bundle transmission line spacer damper are equipped so as to keep the spacing between sub conductors. For 4-conductor bundle the subspan spacing of a spacer damper is determined and applied in order that the bundle may get restored to a normal state when 4-conductor bundle is rolled by rigid body vibration due to wind. But 4 conductors of 345kV 4-conductor bundle transmission line were twisted by the angle of $315^{\circ}$ for the first time korea. In this paper, we will analyze the reason of the power line twisting of 4-conductor bundle which occurred for the first time in korea and offer the preventive countermeasures for this