A Study on Measurement and Analysis of Harmonics in Substation
변전소 고조파 측정 및 분석에 관한 연구
- Han Mu-Ho (RIST) ;
- Park Tae-Joon (RIST) ;
- Lee Seung-Hee (RIST) ;
- Lee Chi-Hwan (UIDUK Univ.)
- Published : 2001.07.01
Abstract
Nonlinear loads change the sinusoidal nature of the ac power current, thereby resulting in the flow of harmonic currents in the ac power system that can cause interference with communication circuits and other type of equipment. To minimize the damage, it is needed to limit harmonics current and voltage. Harmonic measurement system was developed to measure individual voltage and current harmonic continuously and save harmonic data on computer. We measured all 154kV feeders in a steel making company substation. Voltage and current distortion limits for general transmission systems was suggested We found some feeders exceeded current distortion limits. As result voltage harmonic exceeded standard limits.