Proceedings of the KSME Conference (대한기계학회:학술대회논문집)
- 2000.04b
- /
- Pages.258-263
- /
- 2000
Performance Analysis and Prior-Treatment of Heat Pump System with Low-Temperature Water Heat Source
저온수열원이용 열펌프시스템의 전처리 및 성능분석
- Published : 2000.04.20
Abstract
River water is higher in temperature than the surrounding environment during the winter. It is highly suitable a heat source for heat pump system. Despite its suitability, however, it is not widely used, due to its fouling and corrosive nature in heat exchanger tubes of evaporator. It is designed prior-treatment system which come into direct contact with the river water, such as auto-seamer, ozone generator for bactericidal test and auto-cleaning system. And it is analyzed treatment effects for its operation. It is designed two-stage compression heat pump system using R-134a with heating load 35.16kW, ad analyzed its performance. As a result it is obtained 3.08 COP when mid-point pressure is 1,200kPa, and bypass ratio of flowing refreigerant to high-stage compressor is 25.1%