Eartqyake-Resistance of SlenderShear Wall With no Boundary Confinement

단부 횡보강이 없는 세장한 전단벽의 내진성능

  • 박홍근 (정회원, 서울대학교 건축학과) ;
  • 강수민 (정회원, 서울대학교 건축학과) ;
  • 조봉호 (정회원, 서울대학교 건축학과) ;
  • 홍성걸 (정회원, 서울대학교 건축학과)
  • Published : 2000.04.01

Abstract

Experimental and numerical studies were done to investigate seismic performance of slender sheat wall with no boundary confinement. 1/3 scale-specimens that model the plastic region of long slender shear walls subjected to combined axial load and bending moment were rested to investigate strength, ductility, capacity of energy dissipation and strain distribution. The experimental results show that the slender walls fail due to early crushing in the compressive boundary, and then have very low ductility. The measured maximum compressive strain is 0.0021, which is much less then 0.004 being commonly used for estimation of ductility. The experimental results indicates that the maximum compressive strain is not a fixed value but is affected by moment gradient along the shear wall height and distance from neutral axis to the extreme compressive fiber.