부공복합화력발전소 기계기초의 오돈균열제어

Temperature Crack Control Foundation in LG IPP Project

  • 양주경 (정회원, 청운대학교 토목환경공학과) ;
  • 조경연 (정회원, LG건설기술연구소) ;
  • 심재홍 (정회원, LG건설기술연구소 대리)
  • 발행 : 2000.04.01

초록

Nonuniform temperature distribution due to hydration heat induces thermal stress in mass concrete. At early ages, such thermal stress may induce thermal cracks which can affect on the durability ad safety of the structure. Steel fiber reinforced concrete may be useful when a large amount of energy has to be absorbed, when a high tensile strength and reduced cracking are desirable, of an improvement of thermal conductivity is desirable. In LG IPP Project, the upper part(50cm) of turbine foundation was replaced with steel fiber reinforced concrete to reduce the thermal crack induced by hydration heat. It was shown that the thermal crack control could be successfully achieved by steel fiber reinforced concrete.

키워드