Diagnosis for Degradation of Transformer Oil by an Optical Fiber Sensor
광섬유 센서를 이용한 변압기 절연유의 열화 진단
- Yi, Sue-Muk (Central Education Institute (KEPCO)) ;
- Kim, Tae-Young (Korea University) ;
- Suh, Kwang-S. (Korea University) ;
- Sung, Man-Young (Korea University)
- Published : 2000.07.17
Abstract
This paper presents the preliminary results on the application of optical fiber sensor(OFS) for the diagnosis of degradation in the transformer oil. An OFS system using a Mach-Zehnder interferometry technique was built to detect attenuation of acoustic signal produced by discharging. With increasing the number of discharging in the insulation oil, the attenuation of acoustic signal became greater. A strong correlation between electrical and acoustic signal intensities from discharge generated in the transformer oil was confirmed by the results reported here.