A study on operating properties of superconducting fault current limiter in the line-to-line fault

선간 단락사고에 대한 초전도 한류기의 동작특성에 대한 연구

  • Choi, Hyo-Sang (Power System Laboratory, Korea Electric Power Research Institute (KEPRI)) ;
  • Hyun, Ok-Bae (Power System Laboratory, Korea Electric Power Research Institute (KEPRI)) ;
  • Kim, Sang-Joon (Power System Laboratory, Korea Electric Power Research Institute (KEPRI))
  • 최효상 (한국전력공사 전력연구원 전력계통연구실) ;
  • 현옥배 (한국전력공사 전력연구원 전력계통연구실) ;
  • 김상준 (한국전력공사 전력연구원 전력계통연구실)
  • Published : 1999.11.20

Abstract

We investigated the current limiting characteristics of resistive and inductive SFCLs with $100{\Omega}$ of quench impedance for a line-to-line fault in the 154 kV transmission system. The fault simulation at the phase angles $0^{\circ}$, $45^{\circ}$, and $90^{\circ}$ showed that the resistive SFCL limited the fault current less than 15 kA without any DC component after one half cycle from the instant of the fault. On the other hand, the inductive SFCL suppressed the current below 13 kA, but with $2{\sim}3\;kA$ of DC component which decreased to zero in 6 cycles. We concluded that the inductive SFCL had higher performance in current limiting but the resistive SFCL was better from the view point of DC components.