Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1999.11c
- /
- Pages.585-587
- /
- 1999
A Study Of Reliability Check Method for Generator Field Ground Detectors
발전기 계자 접지 검출회로 신뢰성 점검에 관한 연구
- Cheon, Young-Sik (Korea Plant Service & Engineering Co.Ltd.) ;
- Park, Ho-Chul (Korea Plant Service & Engineering Co.Ltd.) ;
- Won, Hak-Jai (Korea Plant Service & Engineering Co.Ltd.) ;
- Han, Seung-Mun (Korea Plant Service & Engineering Co.Ltd.) ;
- Han, Jeong-Hoon (Korea Plant Service & Engineering Co.Ltd.)
- Published : 1999.11.20
Abstract
The rotorbody and rotor winding of generator are isolated by an insulator and the output characteristic of the generator is maintained in the best states. Only when an insulation resistance between them is over a certain extent. The aim of this research is to develop the simulator for rotor earth fault detection circuits. It is composed of the power resource which is to control the virtual field voltage, stepping motor which is to give virtual ground. It is possible to inspect with the device and program developed in this study in the same as real operating condition and evaluate the integrity of generator rotor through the function of data acquisition and graphic output. If these technologies will be applied to the inspection, prevent a damage of the generator and contribute to improve maintenance reliance.
Keywords