The Measurement and Analysis The Electromagnetic Wave by Discharge in Air for Insulation Diagnosis
절연진단을 위한 기중방전에서의 방사전자파 측정과 분석
Abstract
This paper offer fundamental ones about insulation diagnosis with electromagnetic wave, when discharges occurred. To simulate Partial-Discharge(PD), It is used needle-plane electrode in air. As the voltages applied, measure the electromagnetic wave with monopole antenna and analysis its fundamental characteristics, then, acquired data were operated. The results presented as the form of graph, and the magnitude of charge when occurred PD simultaneously. In conclusion, when the magnitude of charge over 100[pC], the electric field strength changed, and then the magnitude of charge and the electric field strength increased samely.
Keywords