초고압 GCB 소호부내의 열가스 유동해석

Analysis of the hot gas flow field in a interrupter of UHV GCB

  • 송기동 (한국전기연구소 스위치기어연구팀) ;
  • 박경엽 (한국전기연구소 스위치기어연구팀) ;
  • 이병윤 (한국전기연구소 스위치기어연구팀)
  • 발행 : 1999.07.19

초록

This paper presents an arc(hot-gas flow field) analysis method in GCB. This method includes the Lorentz's force due to magnetic field, turbulent viscous effect and radiation heat transfer which are indispensable to the analysis of hot-gas flow. To verify the applicability of the Proposed method, steady state hot-Eas flow analysis within a simplified interrupter has been carried out. Inlet boundary pressure values were assumed to be 9.0atm and 12.0atm. For each inlet boundary condition, three cases of hot-gas flow field analyses were performed according to the values of arc currents which were assumed to be D.C 0.6kA. 1.0kA and 2.0kA. The results revealed that the arc radius at nozzle throat has been concentrated by increasing the pressure of nozzle upstream and that the maximum temperature of arc core has been decreased along to nozzle exit and the high temperature lesion come to be wide in nozzle downstream. From these results, it is confirmed that the proposed method will be applicable to predict the large current interruption capability of GCB.

키워드