당진 화력발전소용 800kV 가스절연차단기(Gas Insulated Switchgear) 고유모드해석

The Normal Mode Analysis of 800kV Gas Insulated Switchgear(GIS) for the Dangjin Thermal Plant

  • 신익호 (주식회사 효성 중공업연구소) ;
  • 송원표 (주식회사 효성 중공업연구소) ;
  • 권기영 (주식회사 효성 중공업연구소)
  • 발행 : 1999.07.19

초록

800kV GIS(Gas Insulated Switchgear) was first developed by Hyosung Corporation in Korea at Dec. 1998 and is going to be installed first in the Dangjin Thermal Plant. We intoned to verify the structural safety of 800kV GIS under seismic load. The modal analysis of 800kV GIS has been carried out to obtain the natural frequency and mode shape. PATRAN was used for mode)ing exactly 800kV GIS Geometry. 800kV GIS FE(Finite Element) model was constructed of shell elements for the enclosures and beam elements for the conductors and the support insulators NASTRAN was used for analyzing the normal modes of 800kV GIS FE model.

키워드