송전선로측 권선형 변성기 사용에 따른 기술적 고찰
A Study on the Application of Voltage Transformer at Transmission Lines
- Choi, Ky-Youl (Korea Power Engineering Company, Inc.) ;
- Park, Moon-Bin (Korea Power Engineering Company, Inc.)
- 발행 : 1999.07.19
초록
Recently. due to the drastic development of communication method between substations for pilot protective relaying system. The power line carrier(PLC) application is getting obsolete. Consequently, the coupling capacitor voltage transformer (CCVT) loses its necessity for the carrier coupling function, and so wound voltage transformer(VT) can be used to substitute CCVT for voltage signal. However, VT has been reported to give rise to ferro-resonance phenomena, so sufficient consideration on applying the VT to line side is required. This study introduces probable technical problems in using the VT on T/L side, and carries out feasibility study on the basis of modeling results by EMTP(Electro-magnetic transient program)