Comparison of Nondestructive and Destructive Tests in High Voltage Motor Stator Windings

고압전동기 고정자 권선에서 비파괴와 파괴시험의 비교

  • Published : 1999.07.19

Abstract

Nondestructive and destructive tests were performed the stator windings of three high voltage motors prior to the rewind. Nondestructive tests included ac current increase rate($\Delta$I), dissipation factor(${\Delta}tan{\delta}$), and maximum partial discharge(Qm) The destructive tests included breakdown at three phases with ac voltage. Flashover occurred between the connected winding of endwinding and the stator flame. In two cases creeping discharge occurred between the individual phase windings and the wedges In the stator ends. The results of destructive tests could rarely be determined the breakdown voltage.

Keywords