EMTP Simulation of Bipolar HVDC System

바이폴 HVDC 시스템의 EMTP 시뮬레이션

  • Published : 1998.07.20

Abstract

Using EMTP model which describes bipolar HVDC system, switching level simulation results are presented in this paper. Voltage synchronization at point of common coupling, gate pulse generation and current control loops are represented in TACS module. The system consists of 100 km submarine cable rated 300 MW and 12 pulse rectifier and inverter stations which are connected to equivalent three-phase sources and loads through the 154 kV AC lines, respectively. In convertor stations, harmonic filters and capacitor banks are equipped to cancel out the harmonics generated by converters and to supply the required reactive power.

Keywords