The first report of a study for Field Diagnosis of Large High Voltage Motors

대용량 고압전동기 현장진단연구(I)

  • Published : 1998.07.20

Abstract

This report is the first intermediate report of a series of field test result of large high voltage motors. Major specimens were 3.3/6.6kV class pump motor that was installed and operated for public water service by KOWACO(KOrea WAter resources COperation). The capacity of specimen motors were in range of several hundred kVA. Until now, we get the 22 field test result by testing technique discribed in IEEE standards and discharge-map technique reported by Japanese engineers. The test result were varied very wide range, and there was a tendency according to insulation material and manufacture.

Keywords