[$SF_6$] 가스 절연기기내에 도전성 금속이물 존재시 섬락전압에 미치는 영향

Influence of Conducting Particle on the Breakdown Phenomena of $SF_6$ gas in Gas Insulated System

  • 발행 : 1998.07.20

초록

In this work, the behaviours of conducting wire type particles within the coaxial electrode gap energized with high ac voltage have been systematically investigated using charge simulation method. For this, spheroidal charge is adopted as a image charge for the CSM analysis in order to calculate the acquired charge of the particles which are erected on the surface of the outer electrode. For this purpose, the effects of the lengths and diameters of Cu, Al particles in gas insulated system have been studied by a numerical computation and particle lifting voltage, lifting field, breakdown voltage, acquired charge and travelling distance have been considered. From this, we understand that the particle behaviours have different characteristics according to the particle lengths and diameters. And a possible countermeasure, based on the proposed simulation, has been provided with a view to estimating the flashover voltage of $SF_6$ gas under the 1 atm.

키워드