Development of an automatic steam generator level control logic at low power

저 출력시 증기발생기 수위의 자동제어논리 개발

  • 한재복 (한국원자력연구소 계측제어설계) ;
  • 정시채 (한국원자력연구소 계측제어설계) ;
  • 유준 (충남대학교 전자공학과)
  • Published : 1996.10.01

Abstract

It is well known that steam generator water level control at low power operation has many difficulties in a PWR (pressurized water reactor) nuclear power plant. The reverse process responses known as shrink and swell effects make it difficult to control the steam generator water level at low power. A new automatic control logic to remove the reverse process responses is proposed in this paper. It is implemented in PLC (programmable logic controller) and evaluated by using test equipment in Korea Atomic Energy Research Institute. The simulation test shows that the performance requirements is met at low power (below 15%). The water level control by new control logic is stabilized within 1% fluctuation from setpoint, while the water level by YGN 3 and 4 control logic is unstable with the periodic fluctuation of 25% magnitude at 5% power.