A Phase-Domain Equivalent Representation for Electromagnetic Transients Studies

전력계통 과도현상 해석을 위한 상영역에서의 등가축약 기법

  • Jung, B.T. (System Lab., LG Industrial Systems) ;
  • Kim, S.H. (System Lab., LG Industrial Systems) ;
  • Heo, S.I. (System Lab., LG Industrial Systems) ;
  • Ahn, B.S. (System Lab., LG Industrial Systems) ;
  • Hong, J.H. (Dept. of Elec. Eng., Kyungwon Univ.)
  • 정병태 (LG 산전 시스템 연구실) ;
  • 김성희 (LG 산전 시스템 연구실) ;
  • 허성일 (LG 산전 시스템 연구실) ;
  • 안복신 (LG 산전 시스템 연구실) ;
  • 홍준희 (경원대학교 공과대학 전기공학과)
  • Published : 1996.07.22

Abstract

In this paper, a new time-domain reduction method for unbalanced 3 phase power systems will be represented. The impulse response of the system is used to identify a discrete-time equivalent filter model. The model is formulated directly in the phase domain. Each phase has a self-mode equivalent model and two mutual-mode equivalent models. The equivalent model is determined by the transfer function identification technique based on the Prony analysis. The model is implemented in EMTDC and tested with an unbalanced 3 phase network. The result of test showed that the equivalent model is accurate.

Keywords