This paper presents a method for the extraction of the fundamental frequency from transient signals using Prony's analysis. There exists transient voltages and current after a fault including an exponetially decaying do component and harmonics as well as the fundamental frequency. As Prony's analysis uses exponetially decaying functions as basis functions it can extract the fundamental frequency precisely from transient signals. The results of comparison with DFT are also shown.