The Analysis of Operational Characteristics of Inductive High-Tc Superconducting Fault Current Limiter Concerning Harmonic Component

고조파 성분을 고려한 유도형 고온초전도한류기의 동작 특성 해석

  • Yim, Do-Hyon (Dept. of Electrical Engineering, Yonsei University) ;
  • Joo, Min-Seok (Dept. of Electrical Engineering, Yonsei University) ;
  • Chu, Yong (Dept. of Electrical Engineering, Yonsei University) ;
  • Kim, Han-Jun (Dept. of Electrical Engineering, Yonsei University) ;
  • Ko, Tae-Kuk (Dept. of Electrical Engineering, Yonsei University)
  • 임도현 (연세대학교 전기공학과) ;
  • 주민석 (연세대학교 전기공학과) ;
  • 추용 (연세대학교 전기공학과) ;
  • 김한준 (연세대학교 전기공학과) ;
  • 고태국 (연세대학교 전기공학과)
  • Published : 1995.07.20

초록

Inductive high-Tc superconducting fault current limiter using YBCO superconducting ring in the secondary part has many advantages in power networks. It is based on the superconducting to normal transition and this paper describes its operational characteristics and experimental results, especially focused on the harmonic component analysis and recovery time. We fabricated and tested it under various conditions for the analysis of transient fault characteristics. And for the analysis of harmonics we used FFT methods. The superconducting ring was quenched in 240Arms and fault current was effectively limited to the lower current level. In addition, it was fast recovered when the fault condition was removed and after fault the system had odd harmonics.

키워드