Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1995.07b
- /
- Pages.754-757
- /
- 1995
A Study on Ground Fault Detecting System for DC Voltage Line in the Electric Power Plant
발전소 직류전압 전선로 접지검출시스템에 관한 연구
- Lee, H.K. (Dept. of Control & Instr. Eng. Pusan National Univ. of Tech.) ;
- Kim, N.H. (Dept. of Control & Instr. Eng. Pusan National Univ. of Tech.) ;
- Park, C.H. (KEPCO Research Center) ;
- Kim, T.S. (KEPCO Research Center)
- Published : 1995.07.20
Abstract
This system can detect a ground fault point or a bad insulated line by measuring a power plant DC feeder insulation resistance at the uninterruptible power status. And when the power plant DC feeder with low frequency AC signal has a ground fault, this measuring system can keep recording of its ground fault current and phase checked by Z.C.T. Therefore the power plant could protect a unexpected service interruption.