A Compensating Algorithm for the Secondary Current of Iron-cored Current Transformers

철심 변류기 2차 전류 보상 알고리즘

  • Published : 1995.07.20

Abstract

CT saturation may cause protective relays to malfunction. The conventional method to deal with the problem is overdimensioning of the core so that CTs can carry up to 20 times the rated current without exceeding 10 % ratio correction. However, this not only reduces the sensitivity of relays, but also increases the CT core size. This paper presents a technique of estimating the secondary current corresponding to the CT ratio under CT saturation using the magnetization curve. The proposed algorithm can improve the sensitivity of relays to low level faults and minimize the instability of relays for external faults.

Keywords