• 제목/요약/키워드: water controller

검색결과 352건 처리시간 0.037초

증기발생기 수위제어를 위한 자기동조 퍼지 PID 제어기 개발 (Development of a Self-tuning Fuzzy-PID Controller for Water Level of Steam Generator)

  • 한진욱;이창구;한후석
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제48권10호
    • /
    • pp.1251-1258
    • /
    • 1999
  • The water level control of a steam generator in the unclear power plant is an important process. Most of the water level controllers of the actual plant are PID controllers. But they have limitations in appling for tracking the set point and getting rid of disturbances, so there are some defects to apply in the actual ground even though many research works represented the resolutions to solve it. In this paper, it is suggested that the established simple PID controller in low power has the ability to remove disturbances and trace the set-point, and then possesses the real-time self-tuning function according to the variety of moving peculiarity of a plant. This function realized by making use of fuzzy logic. PID parameters are formulated by a variable ${\alpha}$ and made it fluctuate by a fuzzy inference according to level error and level error change. This mechanism makes application of actual plant effective as well as taking advantage of improving the efficiency of water level controller by way of adding the function of self-tuning instead of replacing PID controller. The computer simulation of this scheme shows the improved performance compare to conventional PID controller.

  • PDF

증기 발생기 수위제어를 위한 모델예측제어기 설계 (Design of Model Predictive Controller for Water Level control in the Steam Generator of a nuclear Power Plants)

  • 손덕현;이창구
    • 대한전기학회논문지:시스템및제어부문D
    • /
    • 제50권8호
    • /
    • pp.376-383
    • /
    • 2001
  • Factors leading to poor control of the steam generator in a nuclear power plant are nonminimum phase characteristics, unreliable of flow measurements and nonlinear characteristics, which increase more at low power(below 20%) operation. And the study of problems for water level control in the steam generator is that design water level controller only power renge, not entire. This paper introduces a model predictive control(MPC) algorithm for solving poor control factors and quadratic programming(QP) for solving input constraints. Also presents the design method of stable model predictive controller in the entire power range. The simulation results show the efficiency of proposed MPC controller by comparing with PI controller, and effect of the design parameters.

  • PDF

발전기 드럼의 수위 지능 제어기 설계 (Water Level Intelligent Controller Design of Power Plant Drum)

  • 홍현문;이봉섭
    • 한국산업융합학회 논문집
    • /
    • 제10권4호
    • /
    • pp.271-274
    • /
    • 2007
  • In this paper, we propose a intelligent controller design method for the water level control of the power plant drum in the form of nonminimum phase system. The proposed method is based on T. Takagi and M. Sugeno's fuzzy model. And we illustrate the improved characteristics as the simulation results, comparing with the conventional the PID and LQ controller design method.

  • PDF

증기발생기 수위 제어를 위한 견실$H^{\infty}$ 제어기 설계 (Design of Robust $H^{\infty}$ Controller for Water Level Control of Steam Generator)

  • 서성환;조희수박홍배
    • 대한전자공학회:학술대회논문집
    • /
    • 대한전자공학회 1998년도 하계종합학술대회논문집
    • /
    • pp.223-226
    • /
    • 1998
  • The control objective of steam generator water level in the secondary circuit of a nuclear power plant is to regulate the water level at the desired set point. The dynamics of steam generators is non-linear in nature. The task of modelling such plant is very difficult and especially so when plant operating conditions change frequently. In these reasons, conventional PI gains over all pover range will not work efficiently and a manual control is generally used in low power operation. Therefore the robust H$\infty$ controller design method should be required. In this paper, we design the robust H$\infty$ controller for water level control of steam generator using a mixed H$\infty$ optimization with model-matching method. Firstly we choose the desired model that has good disturbance rejection performance. Secondly we design a stabilizing controller to keep the model-matching error small and also provide sufficiently large stability margin against additive perturbations of the nominal plant.

  • PDF

핵증기 발생기의 9룰 퍼지논리 제어기 (A 9-Rule Fuzzy Logic Controller of the Nuclear Steam Generator)

  • Lee, Jae-Young;No, Hee-Cheon
    • Nuclear Engineering and Technology
    • /
    • 제25권3호
    • /
    • pp.371-380
    • /
    • 1993
  • 운전원의 언어적인 제어 논리를 이용한 모델과 무관한 제어기가 증기 발생기의 수위 제어를 위해 개발되었다. 오직 9개의 룰을 수위 오차와, 응축 수위 변화를 표현하는 유량 오차로부터 얻어졌다. 벨형의 소속함수는 민감도 분석을 통하여 조절되었고, 결과 과도 상태와 정상상태 공히 양호한 제어성능을 보였다. 저출력에서 전 출력까지의 다단계 출력 증가에 대하여, 전 운전 영역에서 좋은 제어를 보였다.

  • PDF

우수토실에 설치된 월류수 제어를 위한 유입유량조절장치의 개선효과 (Improvements of Inflow Controller Installed in Storm Overflow Diverging Tank for CSOs Control)

  • 임봉수;박윤해;김태응
    • 한국물환경학회지
    • /
    • 제31권4호
    • /
    • pp.428-435
    • /
    • 2015
  • This study was carried out to evaluate the performance of a inflow controller for the control of combined sewer overflows (CSOs). Because of the inflow controller could be adjusted manually by predicting the maximum amount of peak flow, the mechanical adjustment of this controller was higher than the existing fixed-type controller in field application. Standardizing the relationship between the flow and the clearance and angle of an inlet cover plate on the inflow conditions can selected to the optimum conditions for the on-site. It was concluded that BOD pollutant loading at the region in which inflow controller was installed had shown the removal efficiency rate of 42%.

500Ps급 상용차량 디젤엔진을 이용한 선박용 디젤엔진 개발 연구 (A Study for Development of a Marine Diesel Engine from a 500Ps Commercial Vehicle Diesel Engine)

  • 심한섭
    • 한국기계가공학회지
    • /
    • 제12권6호
    • /
    • pp.125-131
    • /
    • 2013
  • This study was carried out to develop a diesel engine for marine propulsion. This marine diesel engine was developed based on a 500Ps vehicle diesel engine. Many main parts, such as the intercooler, radiator, and engine controller were designed for the marine diesel engine. The intercooler was designed to be of sea water cooling type; inlet air is cooled by sea water. Engine coolant is cooled by sea water in the radiator too. The water cooling heat exchanger has high cooling performance. In the cooling system, consists of the intercooler and the radiator, the sea water passes through the intercooler and then the radiator, in sequence. This process is very effective compared to the reverse method in which sea water passes through the radiator and then the intercooler, in sequence. The control performance of the engine controller and the fuel injection rate were improved using an engine speed controller. This system was tested on an engine dynamometer and an exhaust gas analyzer using the marine diesel engine test method. Test results show that the 500Ps marine diesel engine satisfied the IMO NOx regulations; Tier II.

수중운동체 입수 초기의 불안정 거동에 대한 제어기 설계 및 성능평가 (Design and Performance Evaluation of Controller for Unstable Motion of Underwater Vehicle after Water Entry)

  • 박영일;류동기;김삼수;이만형
    • 한국정밀공학회지
    • /
    • 제16권6호
    • /
    • pp.166-175
    • /
    • 1999
  • This paper describes a design and performance evaluation of robust controller which overrides unstable motion and pulls out quickly after water entry of underwater vehicle dropped from aircraft or surface ship. We use 6-DOF equation for model of motions and assume parameter uncertainty to reflect the difference of real motion from modelled motion equation. we represent a nonlinear system with uncertainty as Takagi and Sugeno's(T-S) fuzzy models and design controller stabilizing them. The fuzzy controller utilizes the concept of so-called parallel distributed compensation (PDC). Finally, we confirm stability and performance of the controller through computer simulation and hardware in the loop simulation (HILS).

  • PDF

The μ-synthesis and analysis of water level control in steam generators

  • Salehi, Ahmad;Kazemi, Mohammad Hosein;Safarzadeh, Omid
    • Nuclear Engineering and Technology
    • /
    • 제51권1호
    • /
    • pp.163-169
    • /
    • 2019
  • The robust controller synthesis and analysis of the water level process in the U-tube system generator (UTSG) is addressed in this paper. The parameter uncertainties of the steam generator (SG) are modeled as multiplicative perturbations which are normalized by designing suitable weighting functions. The relative errors of the nominal SG model with respect to the other operating power level models are employed to specify the weighting functions for normalizing the plant uncertainties. Then, a robust controller is designed based on ${\mu}$-synthesis and D-K iteration, and its stability robustness is verified over the whole range of power operations. A gain-scheduled controller with $H_{\infty}$-synthesis is also designed to compare its robustness with the proposed controller. The stability analysis is accomplished and compared with the previous QFT design. The ${\mu}$-analysis of the system shows that the proposed controller has a favorable stability robustness for the whole range of operating power conditions. The proposed controller response is simulated against the power level deviation in start-up and shutdown stages and compared with the other concerning controllers.