• Title/Summary/Keyword: the fire prevention design

Search Result 201, Processing Time 0.028 seconds

Analysis of Temperature Rise and Operation Time of Differential Spot Type Detector in Case of Mattress Fire in Multi-family House (다가구 주택의 매트리스 화재 시 차동식 스포트형 감지기의 온도상승 및 동작시간 분석)

  • Kim, Seo-Young;Kong, Ha-Sung
    • Journal of the Korea Safety Management & Science
    • /
    • v.23 no.3
    • /
    • pp.97-102
    • /
    • 2021
  • This study developed a scenario to understand the reaction rate and operational time according to RTI value of rate of rise detector in each type in case of fire mattress. In the results of analyzing the reaction rate and operational time of detector in each scenario, in case when installing a single detector, the elevated temperature per minute was raised to 8℃/min ~ 9℃/min. In case when installing two detectors, it was raised to 9℃/min ~ 10℃/min. In case when installing three detectors, it was raised to 10℃/min. The horizontal distance between detector and mattress was 1.8m~2.5m. Whenever the number of detectors was increased, the horizontal distance was decreased. The operational time of detector was within maximum 540 seconds and minimum 420 seconds. As the research tasks in the future, there should be the researches on the effects of reaction rate of detector on the evacuation in case of fire through the result value of RSET by setting up the latency until the detector operates, and the researches on the safety by understanding if the operational time of detector is suitable for the evaluation standard of performance-centered design.

Preventing disaster system of the subaqueous tunnel under the Han river in the Bundang railway (분당선 한강 하저터널의 방재시스템)

  • Kim Yong-Il;Hwang Nak-Yeon;Yoon Young-Hoon;Jie Hong-Keun;Jang Sung-Wook;Kim Dong-Hyun
    • Proceedings of the KSR Conference
    • /
    • 2004.10a
    • /
    • pp.308-327
    • /
    • 2004
  • As use of tunnels and subways increase there also are accidents proportionate to it. Daegu Subway Station fire, Hongjimoon tunnel fire led people to be conscious of disaster protection and as a result, there is a trend to adopt standards for fire protection. Accordingly, this thesis is focused on investigating various fire and water protection related issues for subaqueous tunnel under Ran river. The thesis developed evacuation and disaster prevention plan as fire level increases and have identified the suitability of disaster prevention through evacuation and fire simulation, countermeasure of a water leakage during construction and operation considering the subaqueous tunnel. And we selected EPB shield TBM equipment considering the ground condition and effect of boring hole, and accomplished reasonable water protection design through setting goals using event-tree method, as well as examining model test of boring hole and flooding in heavy rain. Also included structured total system consist of water leakage sensing system, water protection gate, pumping system and fire protection system to respond systematically in emergency.

  • PDF

Forecasting Model Design of Fire Occurrences with ARIMA Models (ARIMA모델에 기반한 화재발생 빈도 예측모델의 설계)

  • Ahn, Sanghun;Kang, Hoon;Cho, Jaehoon;Kim, Tae-Ok;Shin, Dongil
    • Journal of the Korean Institute of Gas
    • /
    • v.19 no.2
    • /
    • pp.20-28
    • /
    • 2015
  • A suitable monitoring method is necessary for successful policy implementation and its evaluation, required for effective prevention of abnormal fire occurrences. To do this, there were studies for applying control charts of quality management to fire occurrence monitoring. As a result, it was proved that more fire occurs in winter and its trend moves yearly-basis with some patterns. Although it has trend, if we apply the same criteria for each time, inefficient overreacting fire prevention policy will be accomplished in winter, and deficient policy will be accomplished in summer. Thus, applying different control limits adaptively for each time would enable better forecasting and monitoring of fire occurrences. In this study, we treat fire occurrences as time series model and propose a method for configuring its coefficients with ARIMA model. Based on this, we expect to carry out advanced analysis of fire occurrences and reasonable implementation of prevention activities.

A Study on Data Research for Fire Regulations and Fire Retardant in Interior Architecture (실내건축관련 소방(消防)규정과 방염(防炎)에 관한 연구)

  • Cho, Sung-O;Kim, Yong-Sung
    • Korean Institute of Interior Design Journal
    • /
    • v.19 no.3
    • /
    • pp.95-102
    • /
    • 2010
  • Recently, a grow in size and features of Interior construction work over the complex and The Fire-related regulations have been strengthened for the prevention of fire damage. This study is purpose to propose interior design, construction and supervision for the efficient and reasonable way throughout the fire-related laws are investigated in interior architecture. First, the interior of the building work will be based on actual use Fire-related Laws and Regulations have be investigated. Second, based on analysis of material and facilities by Application can be used in production by the data were applied to the present. Third, the international Fire and Flame Retardant Standards for investigating and reviewing the relevant laws, differences and characteristics of each country were analyzed. Fourth, the various fire-related issues of regulation and the application of relevant provisions in the field works, the law's standards, and improvements were identified by analysis. Fire-Related Laws and Building codes that Safety Administration of the Fire Services are divided into design, it comes to approval from the municipal authorities with concerns about the fire that will fit on the Fire Department's administrative procedures and operations is necessary to integrate operations. In conclusion, Fire-related business are divided into Minister of Land, Transport and Maritime Affairs and Ministry of Public Administration and Security. So, Both institutions is need to be the cooperative work. It is necessary to the field supervision. Because, Flame-resistant performance standards in the field works applied are too complex. Last, Establishment of fire-related regulations will enact by private organizations and the experts to participate.

Evaluation of Design Fire Curves for Single Combustibles in a Cinema Complex (복합영상관 단일 가연물의 디자인 화재곡선 평가)

  • Jang, Hyo-Yeon;Hwang, Cheol-Hong;Oh, Chang Bo;Nam, Dong-Gun
    • Fire Science and Engineering
    • /
    • v.34 no.3
    • /
    • pp.18-27
    • /
    • 2020
  • An actual fire test was performed on single combustibles placed in a local cinema complex, and quantitative differences in the maximum heat release rate (HRR) and fire growth rate were investigated based on the design fire curve methods (i.e., the general and 2-stage methods). In terms of combustible use and fire load, a total of 12 combustibles were selected, classified into cinema lounge and movie theater. It was found that the maximum HRR and fire growth rate determined using the two-stage method were quantitatively different from those of the general method. The application of the two-stage method, which can be used to determine the fire growth rate of the initial fire stage more precisely, could be useful in accurately predicting the activation time of fire detectors and fire-extinguishing facilities, as well as the available safe egress time (ASET) and required safe egress time (RSET).

Revision of the Input Parameters for the Prediction Models of Smoke Detectors Based on the FDS (FDS 기반의 연기감지기 예측모델을 위한 입력인자 재검토)

  • Jang, Hyo-Yeon;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.31 no.2
    • /
    • pp.44-51
    • /
    • 2017
  • Accurate predictions of the activation time for smoke detectors using a fire simulation is are required to ensure the reliability of the RSET (Required Safe Egress Time) calculation in the process of PBD (Performance-Based Design). The objective of this study was to enhance the accuracy of input parameters for the numerical models of smoke detector based on the FDS. To this end, a Fire Detector Evaluator (FDE) developed in previous studies was improved. The uniformities of flow and smoke inside the FDE were improved and accurate measurements of the obscuration per meter (OPM) related to detector operation were also performed through a decrease in the forward scattering of smoke particles. The input parameters using the improved FDE showed a significant difference from the previous FDE quantitatively. In particular, a larger difference was found in a photoelectric detector compared to an ionization detector. Considering that the operating conditions of smoke detectors are affected by the detector type, combustibles, smoke particulars, and color, the database (DB) on the input parameters for various detectors and combustibles should be built to improve the reliability of PBD in future studies.

Analysis of Prediction Results and Grid Size Dependence According to Changes in Fire Area (화원면적 변화에 따른 격자 크기 의존도 및 예측결과 분석)

  • Yun, Hong-Seok;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.33 no.6
    • /
    • pp.9-19
    • /
    • 2019
  • In fire simulations for building fire safety evaluation, changes in the fire area and grid size can significantly influence the prediction results. Therefore, the effects of area changes of the fire source with identical maximum heat release rates on the prediction results of a compartment fire were investigated. The dependence of the prediction results on the grid size using the identical fire area was also examined. No significant changes were observed in the thermal and chemical characteristics of the fires with variable grid sizes, even though the fire area was changed when six or more grids were set based on the fire diameter. In addition, changes in the fire area caused significant differences in the prediction of major physical quantities associated with available safety egress time (ASET) within a compartment. However, the fire area changes did not considerably influence the overall fire characteristics outside the compartment after reaching a certain distance from the opening.

Design and Develop of Automatic Circuit Breaker fot Prevent Secondary Disasters of Fire (화재 2차 피해 예방을 위한 자동 전력 차단기의 설계 및 개발)

  • Song, Jinho
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2018.10a
    • /
    • pp.12-14
    • /
    • 2018
  • Many posters and advertisements for fire prevention have long been known to warn of the danger of fire. The reason for this warning is that the damage of the fire is large. In addition, if the second damage occurs, the damage will be larger. In this study, we will design an automatic power circuit breaker that automatically cuts off the power if the temperature sensor is set to a certain temperature value and then goes up above that value. This study will minimize the secondary damage of fire.

  • PDF

A Numerical Study on the Effect of Volume Change in a Closed Compartment on Maximum Heat Release Rate (밀폐된 구획실의 체적변화가 최대 열발생률에 미치는 영향에 관한 수치해석 연구)

  • Yun, Hong-Seok;Nam, Dong-Gun;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.31 no.5
    • /
    • pp.19-27
    • /
    • 2017
  • The effects of changes in area and location of fire source, fire growth rate, and volume of compartment on the major fire characteristics, including heat release rate, in closed compartment fires were examined. To this end, a fire simulation using Fire Dynamics Simulator (FDS) was performed for ISO 9705 room with a closed opening. As main result, it was found that the changes in the area and location of fire source did not significantly affect the thermal and chemical characteristics inside the compartment, such as maximum heat release rate, total heat release, maximum temperature at upper layeras well as species concentrations. However, increasinthe fire growth rate and volume of compartment resulted in increase of the maximum heat release rate and total heat release, decrease in the limiting oxygen concentration and increase in the maximum CO concentration. Finally, a methodology for the application of fire growth curves to closed compartment fires was proposed by deriving the correlation of the maximum heat release rate expressed as a function of the fire growth rate and the volume ratio of compartment based on the ISO 9705 room.

A Study on escape using elevators in fire emergency (화재 시 승강기를 이용한 피난에 관한 연구)

  • Chung, Eui-Soo
    • Proceedings of the Safety Management and Science Conference
    • /
    • 2007.11a
    • /
    • pp.55-68
    • /
    • 2007
  • Because of not accepted on escape using elevators in fire emergency has some background. In the background elevator hoistway has turn into smoke spread route in fire. The escape that used an elevator was not able to make ends meet; of the big confusion is expected that cannot control the escape adequately, and do that elevator facilities breakdown possibility by the fire water, the escaper shut in car. Therefore ban on elevator service in fire time as a general rule. Recently, a few company promote super high-rise architecture in the country, a fire disaster prevention and human life safety measures preparation for PBD(A Performance Based Fire Protection Design) are studied concretely. And there is the escape example in fire time that used an elevator in the foreign country. You must promote it so that the escape measures that used enclosed stairway and an elevator in charge of a function of the mutual supplement. The result of this research can be used for establishing the standard and regulation for using elevators in fire emergency.

  • PDF