Simulation of a Resistive Superconducting Fault Current Limiter for Line Faults in the Power Grid (단락사고에 대한 저항형 초전도 한류기의 실계통 시뮬레이션)

  • 최효상;황시돌;현옥배
    • Progress in Superconductivity and Cryogenics
    • /
    • v.1 no.1
    • /
    • pp.28-32
    • /
    • 1999
  • We have performed an EMTDC simulation for the current limiting effects of a superconducting fault current limiter (SFCL). The fault currents in the 154 kV transmission line between the arbitrary S1 and S2 substations increased up to 54 KA and 60 KA during the line-to-line and three phase faults, respectively. The SFCL with 100$\omega$ of resistance after quench limited the currents to less than 17 KA within a half cycle. This limited current is well below the upper limit of a circuit breaker, suggesting that the resistance of the SFCL in the transmission line is sufficient.