• 제목/요약/키워드: seat leak hydrostatic test

검색결과 1건 처리시간 0.015초

원전용 안전등급 밸브의 현장 폐쇄기밀시험 기술에 대한 연구 (Research on the on-site Seat Test Technology for the nuclear safety related valves)

  • 정환석;김태성
    • 한국압력기기공학회 논문집
    • /
    • 제17권1호
    • /
    • pp.8-17
    • /
    • 2021
  • The seat leakage test is required after the maintenance work on the valve seat. Either the test has been performed outside of the plant after cutting the valve from the pipe system or the simplified test has been performed so far. It was unable to perform the test at the plant site because it is hard to make a steady pressure on the valve inlet when it is installed in the pipe. This research aims to perform the leakage test in the nuclear power plant while it is installed in the pipe system. The mock-up test is performed by pressurizing the leak-off pipe on the valve body. The result is compared with traditional test result by pressurizing the valve inlet. Furthermore the chamber mock-up tests are performed under various conditions. The leak rate by the developed test using the leak-off pipe is found to be similar but greater than the leak rate by the existing test method. It implies that the test using the leak-off pipe is more conservative than the existing test. The methodology and the equipment which this paper suggests that on-site seat test is possible and the application of the technology could reduce the time and cost for the valve maintenance work significantly.