• Title/Summary/Keyword: percentage differential relaying

Search Result 14, Processing Time 0.022 seconds

A Current Differential Relaying Algorithm for Bus Protection Using a Compensating Algorithm of Secondary Currents of CTs (변류기 전류보상 알고리즘을 이용한 모선보호용 전류 차동계전 알고리즘)

  • Gang, Yong-Cheol;Yun, Jae-Seong;Kim, Dong-Yong
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.9
    • /
    • pp.446-450
    • /
    • 2000
  • A conventional variable percentage current differential relaying algorithm for bus protection may misoperate for external faults with severe CT saturation and internal faults with high impedance. This paper proposes a percentage differential current relaying algorithm for bus protection combined with a compensating algorithm of secondary currents of CTs. Even though CTs are saturated and their secondary currents are severely distorted, the proposed relaying algorithm does not only misoperate for external faults with CT saturation but also detects the internal faults with high fault impedance. Thus, the method improves the sensitivity of the relays and does not require any counterplan for CT saturation.

  • PDF

A Percentage Differential Current Relaying Algorithm for Bus Protection Using Current Transformer Saturation Detecting Algorithm (변류기 포화검출 알고리즘을 적용한 모선보호용 비율전류차동 계전방식)

  • Kang, Yong-Cheol;Yun, Jae-Sung;Ok, Seung-Hun
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.115-117
    • /
    • 2001
  • A percentage current differential relaying algorithm is widely used for bus protection. However, it may maloperate external faults with CT saturation. This paper proposes a percentage current differential relaying algorithm for bus protection using CT saturation detecting algorithm. The CT saturation detecting algorithm uses difference of secondary current of CT and detects CT saturation. The proposed method distinguishes percentage differential relay operation caused by faults from percentage differential relay operation caused by CT saturations.

  • PDF

A Percentage Currant Differential Relaying Algorithm for Bus Protection Using an Advanced Compensation Algorithm of the Secondary Current of CTs (개선된 변류기 2차 전류 보상알고리즘을 적용한 모선보호용 비율전류차동 계전방식)

  • Kang, Yong-Cheol;Yun, Jae-Sung;Lim, Ui-Jai
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.9-11
    • /
    • 2002
  • This paper proposes a percentage current differential relaying algorithm for bus protection using an advanced compensation algorithm of the secondary current of CTs. A percentage current differential relaying algorithm may maloperate in case of external faults with CT saturation. Thus, it needs an additional method to cope with CT saturation. The advanced compensation algorithm is unaffected by a remanent flux. The proposed relaying algorithm does not need any additional methods for CT saturation and is unaffected by the remanent flux and has the wide operating zone of current differential relays.

  • PDF

Performance Improvement of Protective Relaying for Large Transformer by Using Voltage-Current Trend and Flux-Differential Current Slope Characteristic (전압-전류 추이와 자속-차전류 기울기 특성을 이용한 변압기 보호계전기법의 성능 개선)

  • Park, Chul-Won;Park, Jae-Sae;Jung, Yun-Man;Ha, Kyung-Jae;Shin, Myong-Chul
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.53 no.2
    • /
    • pp.43-50
    • /
    • 2004
  • Percentage differential characteristic relaying(PDR) has been recognized as the principal basis for power transformer protection. Second harmonic restraint PDR has been widely used for magnetizing inrush in practice. Nowadays, relaying signals can contain 2nd harmonic component to a large extent even in a normal state, and 2nd harmonic ratio indicates a tendency of relative reduction because of the advancement of material. Further, as the power system voltage becomes higher and more underground cables are used, larger 2nd harmonic component in the differential current under internal fault is observed. And then, conventional 2nd harmonic restraint PDR exposes some doubt in reliability. It is, therefore, necessary to develop a new algorithm for performance improvement of conventional protective relaying. This paper proposes an advanced protective relaying algorithm by using voltage-current trend and flux-differential current slope characteristic. To evaluate the performance of the proposed algorithm, we have made comparative studies of PDR, fuzzy relaying and DWT relaying. The paper is constructed power system model including power transformer, utilizing the WatATP, and data collection is made through simulation of various internal faults and inrush. As the results of test, the new proposed algorithm was proven to be faster and more reliable.

A Comparative Analysis of Fuzzy Logic-Based Relaying and Wavelet-Based Relaying for Large Transformer Protection (대용량 변압기 보호용 퍼지논리 계전기법과 웨이브렛 계전기법의 비교 분석)

  • Park, Chul-Won;Park, Jae-Sae;Shin, Myong-Chul
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.52 no.4
    • /
    • pp.179-188
    • /
    • 2003
  • Percentage differential characteristic scheme has been recognized as the principal basis for large transformer protection. Nowadays, relaying signals can contain second harmonic component to a large extent even in a normal state, and second harmonic ratio indicates a tendency of relative reduction because of the advancement of transformer's core material. And then, conventional second harmonic restraint differential relaying exposes some doubt in reliability. It is, therefore, necessary to develop a new algorithm for the effective and accurate discrimination. This paper deals with advanced fuzzy logic based relaying by using flux differential, and a new fault detection criterion logic scheme by using wavelet transform. To comparative analysis of proposed techniques, the paper constructs power system model including power transformer, utilizing the EMTP, and collects data through simulation of various internal faults and magnetizing inrush. The proposed fuzzy relaying and a new fault detection scheme were tested. The former, fuzzy relaying, was proven to be faster and more reliable than the latter.

Advanced Protective Relaying Algorithm by Flux-Differential Current Slope Characteristic for Power Transformer (전력용 변압기용 자속-차전류 기울기 특성에 의한 개선된 보호계전 알고리즘)

  • 박철원;신명철
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.7
    • /
    • pp.382-388
    • /
    • 2004
  • The most widely used primary protection for the internal fault detection of power transformers is current percentage differential relaying(PDR). However, the harmonic components could be decreased by magnetizing inrush when there have been changes to the material of iron core or its design methodology. The higher the capacitance of high voltage status and underground distribution, the more differential current includes the second harmonic component during occurrence of an internal fault. Therefore, the conventional harmonic restraint methods need modification. This paper proposes an advanced protective relaying algorithm by fluxt-differential current slope characteristic and trend of voltage and differential current. To evaluate the performance of proposed algorithm, we have made comparative studies of PDR fuzzy relaying, and DWT relaying. The paper is constructed power system model including power transformer, utilizing the WatATP99, and data collection is made through simulation of various internal faults and inrush. As the results of test. the new proposed algorithm was proven to be faster and more reliable.

A Percentage Current Differential Relaying Algorithm for Bus Protection Blocked by a CT Saturation Detection Algorithm (변류기 포화 곤단 알고리즘으로 억제된 모선보호용 비율 전류차동 계전방식)

  • 강용철;윤재성
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.1
    • /
    • pp.44-49
    • /
    • 2003
  • This paper describes a percentage current differential relaying algorithm for bus protection blocked by a CT saturation detection algorithm. The detection algorithm blocks the output of a current differential relay only if a differential current is caused by CT saturation in the case of an external fault. Moreover, if a current differential relay operates faster than the detection algorithm, the blocking signal is not ignited. On the other hand. if the detection algorithm operates faster than a current differential relay, the output of the relay is blocked. The results of the simulation show that the proposed algorithm can discriminate internal faults from external faults ever when a CT is saturated in both cases. This paper concludes by implementing the algorithm into the TMS320C6701 digital signal processor. The results of hardware implementation are also satisfactory The algorithm can not only increase the sensitivity of the current differential relay but Improve the stability of the relay for an external faults.

A Study on a Percentage Current Differential Relaying Algorithm for EHV Bus Protection Using a Compensating Algorithm (보상 알고리즘을 이용한 초고압 계통의 모선보호용 비율 전류차동 계전방식에 관한 연구)

  • Kang, Yong-Cheol;Yun, Jae-Sung;Kim, Dong-Yong;Park, Jong-Keun;Moon, Seung-Ill
    • Proceedings of the KIEE Conference
    • /
    • 1999.07c
    • /
    • pp.1139-1141
    • /
    • 1999
  • A variable percentage current differential relaying algorithm is widely used for bus protection. However, it may maloperate in case of high-impedance internal faults and external faults with CT saturation and thus additional method to cope with CT saturation is necessary. This paper proposes a percentage current differential relaying algorithm for bus protection using a compensating algorithm of secondary current of CTs. As the proposed method compensates the distorted secondary currents of CTs it can improves the sensitivity of relays in a large current region and does not need any additional method for CT saturation.

  • PDF

Digital Relaying Algorithm for Power Transformer Protection using Fuzzy Logic Approach

  • Park, Chul-Won;Shin, Myong-Chul
    • KIEE International Transactions on Power Engineering
    • /
    • v.2A no.4
    • /
    • pp.153-159
    • /
    • 2002
  • Power transformer protective relay should block the tripping during magnetizing inrush and rapidly operate the tripping during internal faults. Recently, the frequency environment of power system has been made more complicated and the quantity of 2nd frequency component in inrush state has been decreased because of the improvement of core steel. And then, traditional approaches will likely be maloperate in the case of magnetizing inrush with low second harmonic component and internal faults with high second harmonic component. This paper proposes a new relaying algorithm to enhance the fault detection sensitivities of conventional techniques by using a fuzzy logic approach. The proposed fuzzy based relaying algorithm consists of flux-differential current derivative curve, harmonic restraint, and percentage differential characteristic curve. The proposed relaying was tested with relaying signals obtained from EMTP simulation package and showed a fast and accurate trip operation.

A Percentage Current Differential Relaying Algorithm for Bus Protection Using an Advanced Compensating Algorithm of the CTs (개선된 변류기 보상알고리즘을 적용한 모선보호용 비율전류차동 계전방식)

  • 강용철;윤재성;강상희
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.3
    • /
    • pp.158-164
    • /
    • 2003
  • This paper proposes a percentage current differential relaying algorithm for bus protection using an advanced compensating algorithm of the secondary current of current transformers (CTs). The compensating algorithm estimates the core flux at the start of the first saturation based on the value of the second-difference of the secondary current. Then, it calculates the core flux and compensates distorted currents using the magnetization curve. The algorithm Is unaffected by a remanent flux. The simulation results indicate that the proposed algorithm can discriminate internal faults from external faults when the CT saturates. This paper concludes by implementing the algorithm into a TMS320C6701 digital signal processor. The results of hardware implementation are also satisfactory. The proposed algorithm can improve not only stability of the relay in the case of an external fault but sensitivity of the relay in the case of an internal fault.