• Title/Summary/Keyword: limiter

Search Result 783, Processing Time 0.029 seconds

Analysis for Variation of Limiting Current at Initial Fault Time in Flux-Lock Type SFCL (자속구속형 고온초전도 전류제한기의 사고초기 제한 전류변화 분석)

  • Lim, Sung-Hun;Choi, Hyo-Sang;Gang, Hyeong-Gon;Ko, Seok-Cheol;Lee, Jong-Hwa;Han, Byoung-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.418-420
    • /
    • 2003
  • The fault current limiting characteristics at the initial fault time for flux-lock type high-Tc superconducting fault current limiter(SFCL) were investigated. The amplitude of initial fault current of the flux-lock type SFCL was dependent on the inductance ratio of coil 1 and 2. After fault current limiting mode was analyzed, we compared the calculated value with the experimental one for the initial fault current. The effect of initial fault current due to the inductance ratio of coil 1 and 2 on fault current limiting characteristics was discussed.

  • PDF

Analysis of Characteristics on the High-speed SFCL According to Single Line-ground-fault in the Reclosing Operation (재폐로 동작시 1선 지락사고에 따른 고속도 초전도 한류기의 특성 분석)

  • Jeong, In-Sung;Jung, Byung-Ik;Choi, Hyo-Sang
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.64 no.4
    • /
    • pp.612-615
    • /
    • 2015
  • This paper proposed an high-speed superconducting fault current limiter (H-SFCL). The proposed H-SFCL functioned the initial fault current could be covered by the SFCL and the continued fault current after the one-cycle from fault occurrence could be controlled current-limiting-element of the normal conduction. To investigate the operation characteristics of the H-SFCL, a simulation power system was constructed, and a single line-to-ground fault was occurred. As a result, the H-SFCL limited the fault current by more than about 70%, and it was confirmed that the electric power burden was reduced compared to the SFCL that consisted only of superconductors.

Analysis of Operation Characteristics of OCR and Recloser in Power Distribution System with SFCL (배전계통에 초전도한류기 적용시 OCR 및 Recloser 동작특성 분석)

  • Moon, Jong-Fil
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.61 no.4
    • /
    • pp.214-219
    • /
    • 2012
  • In this paper, the method of protective coordination is studied to install Superconducting Fault Current Limiter (SFCL) to power distribution system. If SFCL is installed, the protective coordination is not operated well because of the decreased fault current. Thus, the resetting method of protective devices is presented to coordinate protection system in power distribution system with resistor-type SFCL. The presented methods are divided into three parts; OCR, OCR-Recloser, OCR-Recloser-Recloser. The presented methods are proved through case studies using PSCAD/EMTDC simulation.

Analysis on Current Limiting Characteristics of Transformer Type SFCL with Additionally Coupled Circuit

  • Lim, Seung-Taek;Ko, Seok-Cheol;Lim, Sung-Hun
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.2
    • /
    • pp.533-539
    • /
    • 2018
  • In this paper, the transformer type superconducting fault current limiter (SFCL) with additionally coupled circuit was suggested and its peak fault current limiting characteristics due to the fault condition to affect the fault current were analyzed through the fault current limiting tests. The suggested transformer type SFCL is basically identical to the previous transformer type SFCL except for the additional coupled circuit. The additional coupled circuit, which consists of the magnetically coupled winding to the primary and the secondary windings together with another superconducting element and is connected in parallel with the secondary winding of the transformer type SFCL, is contributed to the peak fault current limiting operation for the larger transient fault current directly after the fault occurrence. To confirm the fault current limiting operation of the suggested SFCL, the fault current limiting tests of the suggested SFCL were performed and its effective peak fault current limiting characteristics were analyzed through the analysis on the electrical equivalent circuit.

Performance analysis of FH/CPFSK system with the error-correcting code and the diversity under rayleigh fading channel with the thermal noise and the partial-band noise jamming (열잡음과 부분대역재밍이 존재하는 레일레이 페이딩 채널에서 오류정정부호와 다이버시티를 고려한 FH/CPFSK 시스템의 성능분석)

  • 곽진규;박진수
    • The Journal of Korean Institute of Communications and Information Sciences
    • /
    • v.21 no.7
    • /
    • pp.1787-1802
    • /
    • 1996
  • In this paper, the performance for FH/CPFSK system with limiter-discriminator detection and integrage-and-dump post-detection filtering under thermal noie, partial-band noise jamming and rayleigh fading have been analyzed. The method of hard-decision diversity of which the transmitter repeated L times on different hops for each data symbol in a way to mutigate the effects of the jamming has been applied, and the receiver has been combined the L chips. Also, error-correcting code have been applied for improving performance of system. The thermal noise and partial-band noise jamming, intersymbol interference for all eight of the possible adjacent bit data patterns, and FM noise click for evaluating systems have been considered. Also optimum parameters to improve performance of FH/CPFSK system have been obtained and validities have been proved through computer simulation.

  • PDF

ON-OFF' Current Control Method with Frequency Limiter and Operating Characteristics of Brushless DC Motors Using Resolver (리졸버를 사용한 브러쉬 없는 직류전동기의 운전특성과 주파수 제한기를 가진 'ON-OFF'전류제어 방식)

  • 홍성수;권봉환;윤명중
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.35 no.9
    • /
    • pp.396-402
    • /
    • 1986
  • Although the structure of the brushless DC motor is similar to the one of the permanent magnet synchronous motor, its operating characteristics are the same as those of the permanent magnet DC motor. This is the reason that the commutators and brushes in the permanent magnet DC motor can be replaced by the power semiconductor devices and rotor position sensors for the brushless DC motor. In this paper, a current control method is presented to make a sinusoidal current waveform for constant torque generation and the operating characteristics of the brushless DC motor using the resolver as the rotor position sensor is also presented and experimented.

  • PDF

EMTDC simulation for current limiting characteristics of the resistive and inductive SFCL (저항형과 유도형 한류기의 전류제한특성에 대한 EMTDC 해석)

  • 최효상;황시돌;현옥배
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.05a
    • /
    • pp.255-258
    • /
    • 1999
  • We investigated the current limiting characteristics of resistive and inductive SFCLs with 100 $\Omega$ of quench impedance for a single line-to-ground fault. which accounts for about 70% of the total power line faults, in the 154 kV transmission system. The fault simulation at the phase angles 0$^{\circ}$, 45$^{\circ}$, and 90$^{\circ}$ showed that the resistive SFCL limited the fault current less than 15 kA without any DC component after one half cycle from the instant of the fault. On the other hand, the inductive SFCL suppressed the current below 12 KA, but with 3 kA of DC component which decreased to zero in 5 cycles. We concluded that the inductive SFCL had higher performance in current limiting but the resistive SFCL was better from the view point of DC components.

  • PDF

Resistive Hts-Fcl Emtdc Modeling By Using Probabilistic Design Methodology

  • Yoon, Jae-Young;Kim, Jong-Yul;Lee, Seung-Ryul
    • KIEE International Transactions on Power Engineering
    • /
    • v.4A no.2
    • /
    • pp.69-72
    • /
    • 2004
  • Nowadays, one of the serious problems in the KEPCO system is a much higher fault current than the SCC (Short Circuit Capacity) of the circuit breaker. Since superconductivity technology has become more developed, the HTS-FCL (High Temperature Superconductor-Fault Current Limiter) may become an attractive alternative to solving the fault current problem. In order to achieve the best performance, the parameters of HTS-FCL should be designed optimally. Under this setting, this paper presents the optimal design method of parameters for resistive type HTS-FCL using the Monte Carlo technique.

Insulation Design and Testing of HTS coil for 6.6 kV Class HTSFCL (6.6kV급 고온초전도 한류기용 HTS 코일의 절연 설계 및 시험)

  • 백승명;정종만;곽동순;류엔반둥;김상현
    • Proceedings of the Korea Institute of Applied Superconductivity and Cryogenics Conference
    • /
    • 2003.10a
    • /
    • pp.263-268
    • /
    • 2003
  • The Electrical insulation design and testing of high temperature superconducting (HTS) coil for high temperature superconducting fault current limiter (HTSFCL) has been performed. Electrical insulating factors of HTS coil for HTSFCL are turn-to-turn, layer-to-layer. The electrical insulation of turn-to-turn depends on surface length, and the electrical insulation of layer-to-layer depends on surface length and breakdown strength of L$N_2$. Therefore, two basic characteristics of breakdown and flashover voltage were experimentally investigated to design electrical insulation for 6.6㎸ Class HTSFCL. We used Weibull distribution to set electric field strength for insulation design. And mini-model HTS coil for HTSFCL was designed by using Weibull distribution and was manufactured to investigate breakdown characteristics. The mini-model HTS coil had passed in AC and Impulse withstand test.

  • PDF

The Study on Insulation Coordination on 22.9kV SFCL for Applying to Real Grid (22.9kV 초전도 한류기 실계통 적용을 위한 절연협조 검토)

  • Kim, T.H.;Kang, J.W.;Kang, Y.W.;Park, J.W.;Lee, H.S;Yang, B.M.
    • Progress in Superconductivity and Cryogenics
    • /
    • v.14 no.1
    • /
    • pp.20-24
    • /
    • 2012
  • This paper proposes an insulation coordination and surge arrester design for superconducting power system with SFCL(Superconducting Fault Current Limiter) in Icheon substation. In the aspect of the economic analysis, since the superconducting devices are very expensive, the insulation coordination to prevent the dielectric breakdown caused by the lightning surge should be considered carefully. In this paper, the insulation coordination for real grid including SFCL and the design of the protection devices against lightning surge is verified using PSCAD/EM TDC.