• Title/Summary/Keyword: industrial power system

Search Result 2,482, Processing Time 0.037 seconds

Application of medium-voltage drive to motor equipment of 800MW gas power plant. (800MW 가스발전소의 모터 설비에 고압 드라이브를 적용한 사례)

  • Kim, Kyoungsue;Oh, Hyunseok;Park, Jongje;Jeon, Jaehyun;Park, Cheolhyun
    • Proceedings of the KIPE Conference
    • /
    • 2018.07a
    • /
    • pp.424-425
    • /
    • 2018
  • In the introduction, this paper introduces LS Industrial Systems' medium-voltage drive installed at Hyundai Green Power, an 800MW gas power plant. In the body, it explains the synchronous transfer technology and new speed search technology applied to Forced Draft(FD) Fan and Boiler Feed-water(BF) Pump, which are power generation facilities. Lastly, it shows the annual energy saving amount and operation status which are applied to each facility and proves that it is a successful application case.

  • PDF

A STABILITY STUDY FOR INDUSTRIAL PLANTS AND COMMERCIAL FACILITIES (산업용 플랜트 및 상업용 시설물 전력계통의 안정도에 대한 연구)

  • Kim, Ki-Taek;Yoon, Duck-Ro
    • Proceedings of the KIEE Conference
    • /
    • 2005.07e
    • /
    • pp.19-21
    • /
    • 2005
  • The purpose of power system design is, in a word, to provide a good quality of electric power. The design of reliable industrial and commercial power distribution system is important because of the high costs associated with power outage. Three major factors for realization of the purpose are: (1) To hold system frequency at or very close to a specified nominal value(e.g. 60Hz) by control of frequency-effective power. (2) To maintain the correct value of interchange power between power and local generators. (3) To hold system voltage at or very close to a specified nominal value by control of voltage-reactive power. Within the past decade, numbers of industrial and commercial facilities installed with local generation, large motors or both, are increasing. This means that system stability is of concern to a growing number of industrial plant electrical engineers and consultants.

  • PDF

Development of Dissolved Gas Analysis/Diagnosis System with Transformer Fault Test Chamber (I) (변압기 내부 결함 모의시험장치를 통한 유중가스 분석/진단 시스템 개발(I))

  • Kim, Sung-Jik;Seo, Hwang-Dong;Kim, Young-Min;Jung, Jae-Ryong;Yang, Hang-Jun
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.1554-1555
    • /
    • 2011
  • 안정적인 전력공급을 위해 전력설비 진단이 중요시 되고 있고 이를 위해 변전기기인 변압기의 초기고장 검출을 통한 예방진단 기술을 필요로 하고 있다. 변압기 예방진단 기술 중에서도 유중가스진단은 가장 오래되고 신뢰성이 입증된 기술이다. 기존의 유중가스진단법들은 가스비분석법을 이용하고 있는데 대상 가스들이 절연유에의 열화에 의해 발생하는 가스들이고 주위 운전환경에 대한 고려가 부족하여 진단이 불가능하거나 진단오류가 발생한다. 본 연구에서는 절연유뿐만 아니라 고체절연물에 대한 열화를 고려하기 위하여 변압기 내부 결함 모의 시험 쳄버를 제작하고 시험 결과를 바탕으로 진단 알고리즘을 개발하고자 한다.

  • PDF

A Study on Power System Decomposition Technique for Digital Simulation of Large Power System (대규모 계통의 디지털 시뮬레이션을 위한 계통분할 기법이 관한 연구)

  • Lee, Chul-Kyun;Lee, Jin;Kim, Tae-Kyun
    • Proceedings of the KIEE Conference
    • /
    • 2002.11b
    • /
    • pp.171-173
    • /
    • 2002
  • This paper presents a power system decomposition technique for digital simulation of large power system. To decompose power system, distributed transmission line model is used. But this model can be used only for long transmission lines. In this paper, capacitor compensation method is proposed to use distributed transmission line model for short transmission line. And case study shows proposed method can be used for effective power system decompositon in digital simulation of large power system.

  • PDF

Development of 1kW Class PEFC System for Residential Applications (1kW급 가정용 연료전지 시스템 실증 연구)

  • Choi, Dong-Min;Shin, Bum-Su;Park, Yon-Goo;Ham, Mi-Sook;Shim, Jae-Hwi
    • Proceedings of the KIEE Conference
    • /
    • 2008.10c
    • /
    • pp.174-176
    • /
    • 2008
  • HYOSUNG manufactured and tested 1kw class PEFC systems to generate electrical and thermal energy for each residential usage. In particular, HYOSUNG developed Power conditioning system that performs about 91% electrical conversion ratio specified in 1kW class PEFC systems. Prior to system integration, we tested each performances of components to derive control issues from it. In addition, we have been developing the adequate simulator to describe and predict system performance. In this paper, we verified HYOSUNG's 1kW class PEFC systems are valid for residential energy sureces by testing the characteristics of systems and performances of main component.

  • PDF

Characteristices for the Electric Field of Composite Insulator Silicone Shed (Composite Insulator silicone shed 전계특성)

  • Jang, Yoon-Ki;Choi, Sung-Man;Chung, Young-Soo;Lee, Dong-Woen;Kim, Jung-Bae
    • Proceedings of the KIEE Conference
    • /
    • 2008.10a
    • /
    • pp.99-100
    • /
    • 2008
  • Composite insulators are rapidly replacing their porcelain counterparts in electrical substation applications. The composite insulator provide technical and safety ad vantages over other types of insulator. These insulators consist of a FRP(Fiber-reinforced polymer), with two metal flanges and silicone rubber. In this paper, we have investigated the influence of electric field different shaped silicone shed under $SF_6$ gas. As a result, shape of silicone rubber does not effected a electric field. However, the shape of shed can be decided the creepage distance.

  • PDF

A study of ALP for elevator (엘리베이터용 정전시 비상구출장치에 관한 연구)

  • Jang, C.H.;Lee, G.H.;Hur, H.J.;Lee, J.G.;Kim, H.J.;Choi, C.S.;Jeong, J.T.
    • Proceedings of the KIEE Conference
    • /
    • 1997.07f
    • /
    • pp.2013-2015
    • /
    • 1997
  • Elevator stops emergently when power failures happen during operation. In that case, the passenger should wait with frightened in the car untill they are rescued by repair man or power resumes. This paper describes an automatic landing device for power-failure(ALP) that consists of UPS and battery charge control system. The excellence of the ALP operation is verified by experiments in elevator test tower.

  • PDF

Performance Evaluation and Development of the Power Conditioning System for 250kW Molten Carbonate Fuel Cell (250kW급 MCFC용 전력변환기 개발 및 성능평가)

  • Lee, Jin-hee;Son, Ui-kwon;Suh, In-young
    • Proceedings of the KIPE Conference
    • /
    • 2010.11a
    • /
    • pp.261-262
    • /
    • 2010
  • This paper presents the design, development and performance of a power conditioning system (PCS) for application to a Molten Carbonate Fuel Cell (MCFC) for high power generation system. The controller must also supervise the total PCS operation while communicating with the fuel cell system controller. A control method for parallel operation of 250kW PCS was implemented and verified respectively. Experimental performances are compared to minimum target requirements of the PCS for MCFC respectively.

  • PDF

Development of 250kW Power Conditioning System for Molten Carbonate Fuel Cell Power Generation System (250kW급 용융탄산염 연료전지 발전시스템용 전력변환기 개발)

  • Lee, J.H.;Jung, H.J.;Baek, S.T.;Kang, H.H.;Chung, J.M.;Suh, I.Y.
    • Proceedings of the KIEE Conference
    • /
    • 2007.04c
    • /
    • pp.231-233
    • /
    • 2007
  • 본 논문은 신 발전방식 중 하나인 용융탄산염형 연료전지(Molten Carbonate Fuel Cell, 이하 MCFC) 발전시스템에서 생성된 전력을 계통에 안정적으로 변환, 주입하기 위한 계통연계형 전력변환기를 설계, 제작하고 성능 시험을 수행한 결과이다. 250kW급 MCFC 시스템의 정격 사양 및 스택의 운전 형태를 기반으로 250kW급 전력변환기 구조 및 단위기기를 설계하였고 전력변환기는 크게 DC/DC 컨버터부와 DC/AC 인버터부로 구성된다. 본 논문은 MCFC 발전 시스템에 적용되는 전력변환기(Power Conditioning System, 이하 PCS)를 제작하고 성능을 확인하는데 목적이 있다.

  • PDF

Performance Analysis of Supercritical Coal Fired Power Plant Using gCCS Simulator

  • Tumsa, Tefera Zelalem;Mun, Tae-Young;Lee, Uendo;Yang, Won
    • 한국연소학회:학술대회논문집
    • /
    • 2014.11a
    • /
    • pp.37-40
    • /
    • 2014
  • Capturing the carbon dioxide emitted from coal-fired power plants will be necessary if targeted reduction in carbon emissions is to be achieved. Modelling and simulation are the base for optimal operation and control in thermal power plant and also play an important role in energy savings. This study aims to analyze the performance of supercritical coal fired power plant through steady and dynamic simulation using a commercial software gCCS. A whole power plant has been modeled and validated with design data of 500 MWe power plant, base and part load operations of the plant were also evaluated, consequently it had been proven that the simulated result had a good agreement with actual operating data. In addition, the effect of co-firng on the plant efficiency and flue gases were investigated using gCCS simulator.

  • PDF