• 제목/요약/키워드: high voltage cable

검색결과 339건 처리시간 0.028초

유인잠수정 통합형 MVDC 해저케이블 점검시스템 개발 (Development of HVDC Submarine Cable Surveying System with Integrated Pathfinder)

  • 안용호;유희영;이봉희;정길조;정창수;임흥현
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.597-601
    • /
    • 2004
  • HVDC(High Voltage Direct Current) is an underwater cable between Jeju Island and Haenam in main land and supplies approximately $50\%$ of electrical usage in Jeju Island. If there is any power failure due to HVDC, it will cost approximately 50,000 US dollars per day including Thermal Electrical Generation. Therefore it is absolutely necessary to recover the problem in rapid timely basis. Present survey method in Korea is done by scuba diver with air cylinder resulting very poor visual inspection. Other option is by only visual camera attached on miniature ROV for solely suey Purpose. This method does not includeburial depth of cable, cable position, cable condition & etc??‥‥.??? In result, current method does not generate any scientific or sophisticated data which does not allow any intelligent management decision. In conclusion, new method and new systems are needed urgently to upgrade current HVDC underwater cable survey technique in Korea to minimize the cost and time factors.

  • PDF

초초고압 CV Cable용(用) 조립형 직선 접속함에서의 Stress Relief Cone 계면압력 최적화에 관한 연구 (A Study on the Optimization of Interfacial Pressure for the Stress Relief Cone in the Ultra-High Voltage Level Prefabricated Type Joint Box)

  • 백주흠;백승엽;이수길;허근도;박완기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1614-1616
    • /
    • 1998
  • Insulation performance of major components of prefabricated joint such as epoxy insulation unit and premolded rubber cone are guaranteed by material selection design and proper manufacturing. On the other hand insulation performance of the interfaces between the premolded rubber cone and the epoxy insulation unit and the cable insulation is maintained by keeping the premolded rubber cone to close contact with such insulation by spring. Electric characteristics of a interface depend on the contact pressure, but the required characteristics are assured so far as a proper contact pressure is maintained. In this report, the interfacial pressure by pressure sensors both in the early stage and after heating cycle were measured and the simulation by FEM program were presented. The comparison of these two results show that interfacial pressure could be controlled optimally by changing the spring length and lubricant state of the interface.

  • PDF

고압용 XLPE의 유전특성에 관한 연구 (A Study on Dielectric Properties of XLPE for High Voltage)

  • 이용성;이경용;이관우;최용성;박대희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 C
    • /
    • pp.1561-1563
    • /
    • 2004
  • In this paper, we researched the dielectric properties and voltage dependence on slice XLPE sheet from 22[kV] and 154[kV] power cable. We studied effects for impurities and water for semiconductor shield through a dielectric properties experiment to estimate performance of insulating materials in power cable. Capacitance and tan${\delta}$ of 22[kV], 154[kV] were 53/43[pF] and $7.4{\times}10^{-4},\;2.1510^{-4}$. In these results, the trend was increased with the increase of temperature. The tan${\delta}$ of XLPF/ semiconductor layer was increased as compared with that of XLPE. Dielectric properties reliability of tan${\delta}$ was small.

  • PDF

Global Today - 원자력발전소 저전압 케이블의 노화에 대한 적격, 상태 모니터링 및 관리 (1) (QUALIFICATION, CONDITION MONITORING, AND MANAGEMENT OF AGEING OF LOW VOLTAGE CABLES IN NUCLEAR POWER PLANT)

  • 강기식
    • 전기저널
    • /
    • 통권451호
    • /
    • pp.46-58
    • /
    • 2014
  • 2013년 말, 전세계에 운행중인 원자력발전소 원자로는 434기로 총 용량은 371.6GW(e)이며, 이 중 약 80%는 20년 이상 사용되었다. 많은 회원국들은 최우선 순위로 자신들의 원자력발전소 운행 기간을 원래의 예상 기간인 30~40년 보다 길게 허용했다. 그렇다면 원자력발전소의 어려운 환경에서 기존의 케이블을 어떻게 적격 판정할 것인가. 본 원고는 원자력발전소의 저전압 케이블의 적격, 상태 모니터링 및 관리에 대한 연구 사항을 기술하였다.

  • PDF

저밀도 폴리에틸렌의 도전율에 미치는 전자선 조사의 영향 (The Influence of Electron Beam Irradiation due to Conductivity in the Low Density Polyethylene)

  • 조경순;김이두;신현택;이수원;이종필;홍진웅
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1998년도 추계학술대회 논문집
    • /
    • pp.191-194
    • /
    • 1998
  • In this paper, the physical and conductivity properties due to the electron beam irradiation for low density polyethylene using insulating materials of the distribution cable and ultra-high voltage cable are studied. The specimens of the low density polyethylene of thickness 100[$\mu\textrm{m}$] irradiated as each 1 [Mrad], 2[Mrad], 4[Mrad], 8[Mrad], 16[Mrad] and virgin are used in this experiment. In order to measure the conductivity properties, the micro electrometer is used, the range of temperature and app1ying voltage are 20 to 120[$^{\circ}C$], from 100 to 1000[V] respectively So. as a result of the conductivity properties, it is confirmed that the conductivity is increased nearly to 50[$^{\circ}C$], and is not changed until the crystalline melting point from the temperature over 60[$^{\circ}C$] because of the defects of morphology and the formation of many trap centers by means of electron beam irradiation

  • PDF

침 전극에 의한 초고압 케이블 절연재료의 부분방전 특성 (Partial Discharge Characteristics of Ultra-High Voltage Cable Insulators by Needle Electrode)

  • 김균식;최범규;변두균;조경순;김귀열;이충호;홍진웅
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.1
    • /
    • pp.477-480
    • /
    • 2004
  • In other to estimate an electrical properties of the cross linked polyethylene cable, the partial discharge properties due to charge of electrode shape(needle and bar) and void size were investigated at room temperature. Fast trip and breakdown time were appeared by the closed of needle electrode. The trip and breakdown voltage depend on insulator thickness. As the result, confirmed larger effect of void size than effect of insulator thickness. The effect of voids size than influence of insulation thickness was dominated by internal an electrode of inner insulators.

  • PDF

케이블 길이에 따른 HID 램프용 안정기의 특성분석 (Characteristics Analysis of the Ballast for HID Lamps According to Cable Length)

  • 정광현;박종연
    • 조명전기설비학회논문지
    • /
    • 제20권6호
    • /
    • pp.9-17
    • /
    • 2006
  • 본 논문은 선로의 성질에 의한 HID 램프용 안정기의 특성에 대하여 측정 및 분석하였다. 이그니션 전압과 정상 상태의 전압과 전류는 선로의 길이 및 특성에 따라 다르다. 따라서 본 논문에서는 저주파 구동방식 전자식 안정기, 고주파 구동방식 전자식 안정기, 자기식 안정기를 케이블 25[m], 100[m] 거리에서 측정 및 분석 하였다. 여러 종류의 안정기 및 케이블에 대하여 측정 및 분석한 결과에 의해 측정된 안정기들 중 저주파수로 구동되는 전자식 안정기가 가장 적합하고 선간의 캐패시턴스 성분이 중요하다는 결론을 얻었다.

보이드 위치에 따른 XLPE 전계분포 (Electric Field Distribution of XLPE due to Position of Void)

  • 박형준;김균식;신현택;이종필;김귀열;이수원;홍진웅
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 추계학술대회 논문집 Vol.16
    • /
    • pp.220-223
    • /
    • 2003
  • This paper is aimed at determining the e-field distribution by apply voltage of air void, which can be generate air void in the XLPE cable for ultra high voltage. E-field distribution had an effect in XLPE due to the type and position of void, compared and studied. This method of analysis is based on the quasi-static electromagnetic 3D simulation program by boundary element method (BEM): Applied AC 3[kV], discretization of 2000 elements, 4 angular periodicity, The result of experiment indicate that E-field distribution appeared the highest levels on the void position of electrode 2[nm] outer boundary and shape of the smallest inner angle in the void. This will serve to explain the XLPE cable degradation studied of possible, connected cable variation of position and shape of void effects to e-field concentration.

  • PDF

초전도(신)전력계통 고장전류 분석 및 병렬한류시스템 (A fault current analysis and parallel FCL scheme on superconducting new power system)

  • 윤재영;이승렬;김종율
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제8권1호
    • /
    • pp.49-53
    • /
    • 2006
  • This paper specifies the new power supply paradigm converting 154kV voltage level into 22.9kV class with equivalent capacity using superconducting rower facilities and analyze the fault current characteristics with and without HTS-FCL (High Temperature Superconducting-Fault Current Limiter). Superconducting new power system is the power system to which applies the 22.9kV HTS cable in parallel to HTS transformer and HTS-FCL with low-voltage and mass-capacity characteristics replacing 154kV conventional cable and transformer. The fault current of superconducting new power system will increase greatly because of the mass capacity and low impedance of HTS transformer and cable. This means that the HTS-FCL is necessary to reduce the fault current below the breaking current of circuit breaker. This paper analyze the fault current and suggests the parallel HTS-FCL scheme complementing the inherent problem of HTS-FCL, that is recovery after quenching is impossible within shorter than a few seconds.

디지털 제어장치의 고출력 전자기펄스에 대한 취약성 사례 분석 (Vulnerability Case Analysis of the High Power Electromagnetic Pulse on Digital Control System)

  • 우정민;주문노;이홍식;강성만;최승규;이재복
    • 한국전자파학회논문지
    • /
    • 제28권9호
    • /
    • pp.698-706
    • /
    • 2017
  • 디지털 제어 시스템에서 주로 사용되는 설비인 PLC(Programmable Logic Controller)와 통신선로에 대한 HPEM(High Power Electromagnetic) 펄스의 노출 위험이 최근 증가되고 있다. 본 연구에서는 서로 다른 주파수 대역을 가지는 HPEM 발생장치를 이용하여 분리된 독립 객체로써 전자 장치의 HPEM에 대한 취약성을 평가하였다. 전자장치가 어떠한 영향을 받는지 상황별로 나누어 비교하였고, HPEM에 노출된 피 시험 기기의 취약성을 분석하였다. 피 시험 기기는 특정 이상의 HPEM에 노출되면, 제어 장치의 전압 및 통신 파형에 왜곡된 특성을 보였으며, UTP(Unshielded Twisted Pair) 케이블에 연결된 장치는 유도전압에 의해 작동 불량을 나타났다. 그러나 FTP(Foiled Twisted Pair) 케이블에 연결된 장치인 경우에는 HPEM 노출로부터 효율적으로 보호되었다. 따라서 현재 전력설비 및 산업현장에서 이용되고 있는 디지털 제어시스템에 대한 HPEM 노출 취약성과 보호대책의 필요성을 입증하였다.