The Analysis of Ground Potential Rise for Shapes of Grounding Electrode Using Hemispherical Grounding Simulation System (반구형 접지모의시스템을 이용한 접지전극의 형상에 따른 대지전위상승의 분석)

  • Gil Hyoung-Jun;Choi Chung-Seog;Lee Bok-Hee
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.7
    • /
    • pp.319-325
    • /
    • 2005
  • In order to analyze ground potential rise of grounding system installed in buildings, the hemispherical grounding simulation system has been designed and fabricated as substantial and economical measures. Ground potential rise(GPR) has been measured and analyzed for shapes of grounding electrode using the system in real time. The system is apparatus to have a free reduced scale for conductor size and laying depth of a full scale grounding system and is constructed so that a shape of equipotential surface is nearly identified a free reduced scale with a real scale when a current flows through grounding electrode. The system was composed of a hemispherical water tank, AC Power supply, a movable potentiometer, and test grounding electrodes. The test grounding electrodes were fabricated through reducing grounding electrode installed in real buildings such as rod type, mesh grid type. When a mesh grid type was associated with a rod type, GPR was the lowest value. The proposed results would be applicable to evaluate GPR in the grounding systems. and the analytical data can be used 0 stabilize the electrical installations and prevent the electrical disasters.

Distribution of Potential Rise as a Function of Shape of Grounding Electrodes

  • Gil, Hyoung-Jun;Choi, Chung-Seog;Kim, Hyang-Kon
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.4
    • /
    • pp.73-79
    • /
    • 2007
  • In order to analyze the potential rise of grounding systems installed in buildings, a hemispherical grounding simulation system was studied. Potential rise was measured and analyzed regarding the shape and distance of the grounding electrodes by using this system. The system was composed of a hemispherical water tank, AC power supply, a movable potentiometer, and test grounding electrodes. The potential rise was measured in real time by the horizontal moving probe of be potentiometer. The test grounding electrodes were fabricated through reducing the grounding electrode installed in real buildings such as the ground rod, grounding grid and so on. The potential rise was displayed in a two-dimensional profile and was analyzed regarding the shapes of the ground electrodes. The potential rise of the grounding grid combined with a ground rod was the lowest of every grounding electrode tested. The proposed results can be applicable to evaluating ground potential rise in grounding systems, and the analytical data can be used to stabilize the electrical installations and prevent electrical disasters.

A Study on the Agent (Protective Device)-based Fault Determination and Separation Methodology for Smart Grid Distribution System

  • Ko, Yun-Seok
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.1
    • /
    • pp.102-108
    • /
    • 2015
  • This paper proposes a new fault isolation methodology for a smart protective device which plays an agent role on the smart grid distribution system with the distributed generation. It, by itself, determines accurately whether its protection zone is fault or not, identifies the fault zone and separates the fault zone through the exchange of fault information such as the current information and the voltage information with other protective devices using bi-directional communication capabilities on the smart grid distribution system. The heuristic rules are obtained from the structure and electrical characteristics determined according to the location of the fault and DG (Distributed Generation) when faults such as single-phase ground fault, phase-to-phase short fault and three-phase short fault occur on the smart grid distribution system with DG.

VPI-based Control Strategy for a Transformerless MMC-HVDC System Under Unbalanced Grid Conditions

  • Kim, Si-Hwan;Kim, June-Sung;Kim, Rae-Young;Cho, Jin-Tae;Kim, Seok-Woong
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.6
    • /
    • pp.2319-2328
    • /
    • 2018
  • This paper introduces a control method for a transformerless MMC-HVDC system. The proposed method can effectively control the grid currents of the MMC-HVDC system under unbalanced grid conditions such as a single line-to-ground fault. The proposed method controls the currents of the positive sequence component and the negative sequence component without separating algorithms. Therefore, complicated calculations for extracting the positive sequence and the negative sequence component are not required. In addition, a control method to regulate a zero sequence component current under unbalanced grid conditions in the transformerless MMC-HVDC system is also proposed. The validity of the proposed method is verified through PSCAD/EMTDC simulation.

Analysis of the Ground Impedance of Ground Grids Combined with the Carbon Ground Electrodes (탄소접지극이 병설된 접지그리드의 접지임피던스의 해석)

  • Lee, Bok-Hee;Um, Sang-Hyun;Kim, You-Ha;Lee, Kang-Soo;Jeon, Byung-Wook;Choi, Jong-Hyuk
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.3
    • /
    • pp.36-42
    • /
    • 2013
  • This paper deals with the frequency-dependent ground impedance of ground grids combined with the carbon ground electrodes. Ground grids are generally valid for multipurpose grounding systems as well as lightning protection systems. The carbon ground electrodes may be supplementarily used to reduce the high frequency ground impedance and to improve the transient response to surge currents. The frequency-dependent ground impedances of ground grids combined with or without the carbon ground electrodes were measured and their simulations with due regard to frequency-dependent soil resistivity were implemented by using EMTP program and Matlab modeling. As a consequence, the ground impedance of ground grids combined with the carbon ground electrodes is significantly reduced when the test current is injected at the terminal of the carbon ground electrode. The measured and simulated data for the test ground grids fairly agree with each other. It was found that the proposed method of simulating the frequency-dependent ground impedance is distinguished. The simulation techniques of predicting accurately the ground impedances without actual measurements can be used in the design of grounding systems based on ground grids and the carbon ground electrodes.

Impulse Ground Impedances of a Deeply Driven Ground Rod Combined with Different Shape Grounding Electrodes (형상이 다른 접지전극에 접속된 심매설 봉상 접지전극의 임펄스접지임피던스 특성)

  • Lee, Bok-Hee;Lee, Su-Bong;Chang, Keun-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.2
    • /
    • pp.63-68
    • /
    • 2005
  • This paper describes the characteristics of effective impulse ground impedance of deeply driven ground rods combined with grounding grid or counterpoises with needles. The potential rises of the test ground electrodes were measured as a function of the rise time of applied impulse currents and the effective impulse ground impedances were calculated The impulse ground impedances of deeply driven ground rods strongly depend on the rise time of impulse currents and significantly reduced by the connection of grounding grids in parallel.

A Study on Geotechnical Lineament Analysis by Image Processing Method (영상사진을 이용한 지반공학적인 선구조분석 연구)

  • 이수곤;금동헌
    • Proceedings of the Korean Geotechical Society Conference
    • /
    • 2000.11a
    • /
    • pp.593-600
    • /
    • 2000
  • Most of ground investigations can be grasped geological distribution which like rock name, geological structure, soil condition, underwater condition, land slide, ground cave-in, ground collapse by geological survey. But geological survey is limited to part region geological structure, not wide region. Therefore, Image Processing Method must need to grasp wide region geological structure. The object of this research is presented analysis data of geotechnical engineering in first step investigation.

  • PDF

Frequency-Variant Power and Ground Plane Model for Electronic Package (패키지의 주파수 의존형 파워 및 그라운드 평판 모델)

  • 이동훈;어영선
    • Proceedings of the IEEK Conference
    • /
    • 1999.06a
    • /
    • pp.385-388
    • /
    • 1999
  • A new frequency-variant equivalent circuit model of power/ground plane is presented. The equivalent circuit is modeled with grid cells. The circuit parameters of each cell were extracted by using Fasthenry. To verify the developed circuit model, its s-parameters are compared with the measured s-parameters 〔2〕 and the full-wave simulation-based s-parameters. Consequently, it is shown that our frequency-variant equivalent circuit model can accurately predict imperfect ground effects under the high frequency operation of electronic package.

  • PDF

A Study on Behavior Characteristics of Soft Ground by DCM Arrangement Type (DCM 배치 형상에 따른 연약지반 거동 특성에 관한 연구)

  • You, Seung-Kyong;Lee, Jong-Young;Hong, Gigwon
    • Journal of the Korean Geosynthetics Society
    • /
    • v.20 no.4
    • /
    • pp.125-131
    • /
    • 2021
  • This study described the relationship of settlement-lateral displacement and settlement-heaving according to the DCM type using the model test results, in order to evaluate the behavioral characteristics of the soft ground improved with DCM. As a result, it was found that the total settlement of the model ground was relatively small in the soft ground, to which the DCM was applied, and the settlement was less in the order of the grid type, wall type, and pile type under the same load conditions. This trend was also the same for the lateral displacement and heaving. In addition, the relationship between settlement and lateral displacement of soft ground was analyzed to be similar to that of previous study (Leroueil et al., 1990). Therefore, the DCM of grid type was evaluated to be superior to other types for lateral flow and heaving in the improvement effect of soft ground.

A Technic to Improve and Implement Virtual Environment Grid Information in War-game Model (워게임모델의 가상환경격자정보 개선과 구축 기법)

  • Choi, Beyoung-Moo;Yang, Hae-Sool
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.10 no.4
    • /
    • pp.785-794
    • /
    • 2009
  • We studied on a technic to improve and implement the virtual environment grid information in the war-game model. The virtual environment data are categorized into ground, sea, and air, and separatedly managed and operated. The data are implemented and managed in the geographical information and topography type information. The geographical information, including grid location coordinate and sea level, are managed in computer files as a grid type. We improved the representation of the sea level by mapping the sea level value of the grid information file into GCV and suggested the dynamic virtual environment implementation technic for the region with the large range of tide. In the experiments, we could know that it is possible to adopt the dynamic virtual environment to the war-game model.