• 제목/요약/키워드: geothermal system

검색결과 569건 처리시간 0.024초

지반 투수계수와 양수량 조건이 복수정 지열 히트펌프 시스템의 성능에 미치는 영향 (The Effect of Soil Permeability and Pumping Rate on Performance of Two-well Geothermal Heat Pump System)

  • 조정흠;남유진
    • 한국지열·수열에너지학회논문집
    • /
    • 제11권4호
    • /
    • pp.28-34
    • /
    • 2015
  • The groundwater heat pump (GWHP) systems have great potential for heating-cooling system which use annual constant groundwater temperature for heat source. Generally, the performance of GWHP system significantly depends on the geological and hydraulic properties such as hydraulic conductivity, thermal conductivity, soil condition so on. Therefore, in order to use GWHP systems efficiently, it is necessary to analyze the effect of design factors on the system performance. However, there are a few researches on the optimum design method for the open-loop geothermal system. In this research, the design factor in the open-loop geothermal system was analyzed quantitatively for the optimal design method by using numerical simulation. As a result, it was found that the temperature change of heat source depends on the design factor.

EGS 지열발전과 저류층 수리자극 기술 (EGS Power Generation and Hydraulic Stimulation)

  • 민기복;송윤호;윤운상
    • 터널과지하공간
    • /
    • 제23권6호
    • /
    • pp.506-520
    • /
    • 2013
  • 지열에너지는 기저부하를 제공하는 신재생에너지이나 현재까지 화산지대에만 대부분의 지열발전이 이루어져 왔다. 인공저류층 지열시스템 (Enhanced Geothermal System, EGS)는 비화산지대의 지열발전을 가능하게 할 개념으로 알려져 있으며 수리자극(hydraulic stimulation)이 핵심기술이다. 본 논문은 EGS지열발전의 개발 현황을 소개하고, 수압파쇄와 수리전단이 주 메커니즘인 수리자극의 핵심원리, 설계변수 및 수리자극에 수반되어 발생하는 미소진동의 원리 및 관측기술을 소개한다. 한국에서의 EGS 지열발전을 위하여 필요한 과제를 소개하여 향후 기술개발의 방향을 제시한다.

수치 시뮬레이션을 이용한 복수정(Two-Well) 개방형 지열 시스템의 열원수 온도 변화 검토 (A Study on the Characteristics of Heat Source Temperature for Two-Well Geothermal System Using Numerical Simulation)

  • 조정흠;남유진
    • 설비공학논문집
    • /
    • 제27권4호
    • /
    • pp.207-212
    • /
    • 2015
  • The use of groundwater and ground_heat is one of the ways to use natural and renewable energy, and it has been considered as a technology to reduce greenhouse gas emissions and increase energy-saving. There are a few researches on the optimum design for the open-loop geothermal system. In this study, to develop the optimal design method numerical simulation of the open-loop geothermal system with two-wells was performed by a groundwater and heat transfer model. In this paper, a study was performed to analyze the system performance according to well distance and pumping flow rate. In the result, average heat exchange rate and heat source temperature were calculated and it was found that they were dependent on the pumping rate.

몽골에서의 지열 시스템 적용을 위한 주택 에너지분석 (Analysis on Housing Energy for Applying Geothermal System in Mongolia)

  • 김진호;김중헌;신승호
    • 한국지열·수열에너지학회논문집
    • /
    • 제10권2호
    • /
    • pp.19-23
    • /
    • 2014
  • In the capital of Mongolia where the air quality is getting worse due to the coal consumption used for electricity generation and district heating, the application of geothermal systems in the housing sector is recently designed for high class resort. In this study, the case of applying a geothermal system in a house in Mongolia is examined. The effects of passive house design on the needed heat pump capacity, as well as the annual energy consumption are analyzed. Moreover, as the initial costs, except labor fee, are assumed similar to Korea, cost analysis for several cases is examined, too. From the results, if a house is designed according to passive house standard instead of ASHRAE standard, the heat pump capacity can be expected to be reduced from 16 to 5~6 RT. Furthermore, although the initial cost of architectural cost might increased by 29 M\, the total initial cost is reduced by 14 M\, while the annual energy consumption is reduced by 14%. This is mainly driven by the fact that the geothermal system which serves as the main system to cover the building needs, with a high initial cost for fulfilling the peak requirements.

석모도 지열수 개발을 위한 자기지전류탐사의 적용 (Application of magnetotelluric survey for development of deep geothermal water at Seokmo Island, Korea)

  • 이태종;송윤호;박덕원
    • 한국지열·수열에너지학회논문집
    • /
    • 제4권1호
    • /
    • pp.1-10
    • /
    • 2008
  • A magnetotelluric survey and geological survey have been performed to delineate deeply extended fracture systems at the geothermal field in Seokmo Island, Inchon, Korea. One borehole(BH-1) succeed to meet a large fracture system at the depth of 750 m where approximately $72^{\circ}C$ geothermal water is overflowing, while the other borehole(BH-2), which is about 200 m eastward from BH-1, failed to develop enough geothermal water even at the depth of 1,200m. Though there have been so many electric noise sources around the survey region, good quality of MT data above 1 Hz could be obtained with careful installation, remote reference processing. Inversion of MT data for two lines roughly perpendicular to the two major lineaments respectively show that the two lineaments are related to the fracture systems that are extended at least down to 1.5 km depth and inclined eastwards. From the interpretation, additional drilling for BH-2 is recommended and finally meet the fracture systems at the depth of 1,280 m and resulted in overflow of large amount of geothermal water of temperature $69.4^{\circ}C$ from BH-2.

  • PDF

열원의 온도변화에 따른 겨울철 태양열-지열 하이브리드 R22 열펌프의 성능에 관한 해석적 연구 (Theoretical Study on the Performance in a Solar-Geothermal Hybrid R22 Heat Pump During Winter Season according to Heat Source Temperature)

  • 강변;조홍현
    • 한국지열·수열에너지학회논문집
    • /
    • 제8권4호
    • /
    • pp.24-31
    • /
    • 2012
  • The Solar and geothermal energy have many advantage like low cost, non-toxic, and unlimited. But those the have very low energy efficiency. In this study, the theoretical study of performance in a sola-geothermal hybrid heat pump with operating conditions has carried out. As a result, as the solar radiation increases from 1 $MJ/m^2$ to 20 $MJ/m^2$, the heat pump operating time decreases by 19.5% from 18 times to 14.5 times and the heat pump heat decreases by 23%. Besides, the heating COP increases by 21.4% when the evaporator inlet temperature increases from $11^{\circ}C$ to $19^{\circ}C$. By adapting the geothermal system into a solar hybrid R22 heat pump, the system performance and reliability increases significantly for variable operating conditions during winter season.

캐스케이드 열펌프시스템의 운전 특성에 관한 연구 (A Study on the Operating Performance of a Cascade Heat Pump)

  • 장기창;백영진;나호상;김지영;이재훈
    • 한국지열·수열에너지학회논문집
    • /
    • 제5권1호
    • /
    • pp.7-11
    • /
    • 2009
  • The purpose of this study is to investigate the performance of a water heat source cascade heat pump system R717(Ammonia) is used for a low-stage working fluid while R134a is for a high-stage. In order to gain a high temperature supply water in winter season, the system is designed to perform a cascade cycle. In this study, two experiments were carried out. One is a system starting test from the low load temperature of $10^{\circ}C$. The other is a system performance investigation over the R717 compressor capacity changes. Experimental results show that when it starts from the low load temperature, the suction temperature of the low-stage compressor is higher than that of a high-stage. The system performance increases when a water source temperature or a low-stage compressor rotational frequency goes higher.

  • PDF

우물관정(SCW: Standing Column Well)형 냉난방 시스템의 지중열 해석과 실증 실험에 관한 연구 (Research of geothermal analysis and experimental test for Standing Column Well type system)

  • 권익상;홍기배
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2010년도 춘계학술대회 초록집
    • /
    • pp.173-173
    • /
    • 2010
  • This thesis identified basic design elements (Sustainable Yield, Temperature of Groundwater, Depth of Well, Separation Distance between wells) regarding installation of Standing Column Well, Geothermal Heat pump System by dynamic analysis.

  • PDF

우물관정(SCW: Standing Column Well)형 지열 냉난방 시스템 설계를 위한 지중열 해석에 관한 연구 (Research for geothermal analysis on design of Standing Column Well type system)

  • 권익상;이건중;김태원
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2009년도 추계학술대회 논문집
    • /
    • pp.576-580
    • /
    • 2009
  • This thesis identified basic design elements(Sustained Yield, Depth of Well, Separation Distance between wells) regarding installation of Standing Column Well, Geothermal Heat pump System by dynamic analysis.

  • PDF

지열원 히트펌프를 이용한 도로융설시스템의 CFD 성능예측에 관한 기초연구 (A Basic Study on the Performance CFD simulation of Road Snow-melting system by Ground Source Heat Pump)

  • 최덕인;김중현;김진호;황광일
    • 한국지열·수열에너지학회논문집
    • /
    • 제6권2호
    • /
    • pp.23-28
    • /
    • 2010
  • Fluent ver.6.3 is used as CFD(Computational Fluid Dynamics) simulator to predict the performance of snow-melting system by geothermal pipes energy. As the results of this simulation, it is clearly shown that $50^{\circ}C$ of working fluid in to geothermal evaluated as more effect comparing to $45^{\circ}C$ of working fluid. The Surface temperature is come to $5^{\circ}C$ at 1m/s speed and $50^{\circ}C$ temperature of the working fluid.