• Title/Summary/Keyword: froude scaling

Search Result 29, Processing Time 0.021 seconds

Theoretical Study on the Behavior of Momentum-controlled Buoyant Jet and Flame of Hydrogen (운동량에 의해 제어되는 수소 부양 제트 및 화염의 거동에 관한 이론적 해석)

  • Yang, Won;Kim, Jong-Soo;Won, Sang-Hee;Kim, Min-Kook;Chung, Suk-Ho
    • 한국연소학회:학술대회논문집
    • /
    • 2005.10a
    • /
    • pp.207-214
    • /
    • 2005
  • Hydrogen safety is one of the key technical issue with growing attention on utilization of hydrogen energy. This study is aimed to predict behavior of momentum-controlling buoyant jet and flame caused by hydrogen leakage from a high pressured tank. Approximate solutions were derived for the case of turbulent buoyant jet and diffusion flame in still air. In case of hydrogen jet with low Froude number (100-4000), computed jet trajectories were compared with experimental data and showed good agreement with them. Jet and flame trajectories and flame length of hydrogen are predicted and compared with the buoyant flame of propane. The results well show that buoyancy is dominant in the range of low Froude number, while initial momentum is dominant in the range of high Froude number. That effect is more distinct for hydrogen flame than the case of propane.

  • PDF

An Experimental Study of Smoke Movement in Tunnel Fires (터널화재시 연기 거동에 관한 실험적 연구)

  • Lee, Sung-Ryong;Kim, Choong-Ik;Ryou, Hong-Sun
    • Proceedings of the KSME Conference
    • /
    • 2001.06d
    • /
    • pp.121-126
    • /
    • 2001
  • In this study, reduced-scale experiments were conducted to understand smoke movements in tunnel fires with the natural ventilation. The 1/20 scale experiments were conducted under the Froude scaling since the smoke movement in tunnels is governed by buoyancy force. Six cases of experiments(pool diameter is 6.5cm, 7.3cm, 8.3cm, 10cm, l2.5cm and l5.4cm), in which vertical vents positioned 1m from the fire source symmetrically, were conducted in order to evaluate the effect of the vent on smoke movement. In case of heat release rate under 2MW, smoke front reached to the tunnel exit about 20 see delayed with ventilation and the smoke velocity was proportional to the power of the heat release rate. Temperature after the vent was lower than without vent. In case of l5.4cm pool, the temperature difference was about $50^{\circ}C$. It was confirmed that the thickness of smoke layer was maintained uniformly under the 35% height of tunnel through the visualized smoke flow by a laser sheet and the digital camcoder.

  • PDF

An Experimental Study on the Effect of the Balcony on the Vertical Smoke Movement of the High Rise Building (고층건물의 수직방향 연기거동에 미치는 발코니의 영향에 관한 실험적 연구)

  • Yang Seung-Shin;Kim Sung-Chan;Ryou Hong-Sun;Shim Sang-Hoon
    • Journal of the Korean Society of Safety
    • /
    • v.20 no.1 s.69
    • /
    • pp.42-48
    • /
    • 2005
  • The present study investigates the effect of balcony on external smoke movement of high rise building through the fire tests of the 1/10 reduced model scale using Froude scaling. A hexane pool fire is used to examine the smoke movement for various opening sizes of balcony and temperature distributions are measured by T-type thermocouples. Also, hydrogen bubble technique is applied to visualize the smoke movement near the balcony. Measured temperatures of the closed balcony is 2.5 times higher than those of the open balcony because the external smoke in case of the closed balcony rise along the vertical wall. The maximum vertical temperature of partially closed balcony is similar with fully closed balcony and mean temperature inside of balcony increases as opening size of balcony decreases. The experimental results show that the balcony space plays an important roles in preventing fire propagation and cooling of smoke layer. In order to ensure the fire safety in high rise building design, a series of systematic researches are required to examine the various type of balconies.

A Study on the Calculation of Critical Velocity by Fire Intensity (화재강도에 따른 임계풍속산정에 관한 연구)

  • Kim, Jong-Yoon;Lim, Kyung-Bum;Seo, Tae-Beom;Rie, Dong-Ho;Yoo, Ji-Oh
    • Fire Science and Engineering
    • /
    • v.20 no.4 s.64
    • /
    • pp.91-97
    • /
    • 2006
  • This study was executed to review feasibility on the calculation of critical velocity with a reduced model of an actual tunnel in order to establish the optimum fire protection system for a fire in road tunnels. In a scaled model about 1/29 of an actual tunnel based on the Froude scaling, critical velocity was calculated by visualizing smoke flow and analyzing correlation with temperature. In the experiment, critical velocities at which smoke backflow length became zero showed a small difference within about 5% compared to results calculated by the Kennedy formula, and the relation between smoke flow and temperature distribution appeared similarly without getting greatly influenced by changes in fire intensity.

Flame Length and EINOx Scaling of Syngas $H_2$/CO Turbulent Non-premixed Jet Flames ($H_2$/CO 합성가스의 비예혼합 난류 제트화염에서 화염 길이와 EINOx 스케일링)

  • Hwang, Jeongjae;Sohn, Kitae;Bouvet, Nicolas;Yoon, Youngbin
    • Journal of the Korean Society of Combustion
    • /
    • v.17 no.4
    • /
    • pp.30-37
    • /
    • 2012
  • The flame lengths and NOx emission characteristics of syngas $H_2$/CO turbulent non-premixed jet flames were investigated. The flame length which is the main parameter governs NOx emission was studied for various syngas compositions. The flame length was compared with previous correlation between Froude number and flame height and it shows that they have good agreements. It was confirmed that the turbulent jet flames herein investigated are in the region of buoyancy-momentum transition. NOx emission was reduced with increased Reynolds number and CO contents in syngas fuel and with decreased fuel nozzle diameter which is attributed by decreased flame residence time. Previous EINOx scaling based on flame residence time of $L_f^3/(d_f^2U_f)$ satisfies only the jet flame in momentum-dominated region, not buoyancy-momentum transition region. The simplified flame residence time ($L_f/U_f$) was adopted in modified EINOx scaling. The modified scaling satisfies the jet flames not only in momentum-dominated region but in buoyancy-momentum transition region. The scaling is also satisfied with $H_2$/CO syngas jet flames.

An Experimental Study on the Effect of Ventilation Velocity on the Burning Rate in Longitudinal Ventilation Tunnel Fires (종류식 배연 터널 화재시 배연속도가 연소율에 미치는 영향에 대한 실험적 연구)

  • Yang Seung-Shin;Ryou Hong-Sun;Choi Young-Ki;Kim Dong-Hyeon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.10
    • /
    • pp.914-921
    • /
    • 2005
  • In this study, the 1/20 reduced-scale experiment using Froude scaling were conducted to investigate the effect of longitudinal ventilation velocity on the burning rate in tunnel fires. The methanol pool fires with heat release rate ranging from 2.02 kW to 6.15 kW and the n-heptane pool fires with heat release rate ranging from 2.23 kW to 15.6 kW were used. The burning rate of fuel was obtained by measuring the fuel mass at the load cell. The temperature distributions were observed by K-type thermocouples in order to investigate smoke movement. The ventilation velocity in the tested tunnel was controlled by inverter of the wind tunnel. In methanol pool fire, the increase in ventilation velocity reduces the burning rate. On the contrary in n-heptane pool fire, the increase in ventilation velocity induces large burning rate. The reason for above conflicting phenomena lies on the difference of burning rate. In methanol pool fire, the cooling effect outweighs the supply effect of oxygen to fire plume, and in n-heptane pool vice versa.

An Experimental Study of Smoke Movement in Tunnel Fires with Natural Ventilation (터널화재시 자연환기에 의한 연기거동에 관한 실험적 연구)

  • 김충익;유홍선;이성룡;박현태
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.3
    • /
    • pp.247-253
    • /
    • 2002
  • In this study, reduced-scale experiments were conducted to analyze smoke movement in tunnel fire with roof vent. The 1/20 scale experiments were carried out under the Froude scaling using gasoline pool fire ranging from 7.3 to 15.4 cm in diameter with total heat release rate from 1.0 to 8.46kw. In case of 1 m high vent, smoke front reached to the tunnel exit at about 16 sec delayed with ventilation. The delay time grew longer with the vent height. The temperature after the vent was lower than that without the vent. The exit temperature declined maximum of $20^{\circ}C$ after passing the vent. It was confirmed that the thickness of smoke layer was maintained uniformly under the 25% height of the tunnel through the visualized smoke now by a laser sheet and the digital camcorder.

An Experimental Study of Smoke Movement in Tunnel Fires with Natural Ventilation (터널 화재시 자연 배기에 의한 연기 거동에 관한 실험적 연구)

  • 이성룡;김충익;유홍선
    • Fire Science and Engineering
    • /
    • v.15 no.1
    • /
    • pp.1-6
    • /
    • 2001
  • In this study, reduced-scale experiments were conducted to understand smoke movements in tunnel fires with the natural ventilation. The 1/20 scale experiments were conducted under the Froude scaling since the smoke movement in tunnels is governed by buoyancy force. Three cases of experiments, in which a natural vent location varied from 1 m, 2 m and 3 m from the fire source symmetrically, were conducted in order to evaluate the effect of the position of ventilation systems on smoke movement. In case of a poo1 whose diameter is 4.36 cm, the temperature of smoke layer passed through the vent was maintained 7~$8^{\circ}c$ less than that of smoke layer without a vent. In case of a pool whose diameter is 5.23 cm, the average velocity passed through the vent was decreased when it was close to the fire source. And the maximum delay time was 3.86s. In CASE 1, the ceiling temperature was decreased by approximately 8$^{\circ}C$ and the vertical temperature was decreased by approximately $7^{\circ}c$. In CASE 2, both ceiling and vertical temperature wert decreased by $3^{\circ}c$ and in CASE 3, they were decreased by $2^{\circ}c$ each. It was confirmed that the thickness of smoke layer was maintained uniformly under the 25% height of tunnel through the visualized smoke flow by a laser sheet and the digital camcoder.

  • PDF

An Experimental Study on Aircraft Internal Store Separation Characteristics (항공기 내부무장 분리특성 분석을 위한 풍동시험연구)

  • An, Eunhye;Cho, Donghyun;Kim, Jongbum;Jang, Youngil;Jeong, KyeongJin;Kim, Sangjin;Lee, Hokeun;Reu, Taekyu;Chung, Hyoungseog
    • Journal of the Korea Institute of Military Science and Technology
    • /
    • v.20 no.1
    • /
    • pp.81-89
    • /
    • 2017
  • This study investigates store separation characteristics of an unmanned aerial vehicle having generic stealth configuration over unsteady flow of an internal bay. Free-drop wind tunnel tests are conducted to simulate bomb releases from an internal weapons bay while high-speed camera images are taken. The images are analyzed to examine the effects of flow velocity, angle of attack, flap deflection and the ejector force application on the store separation trajectories. For the free-drop wind tunnel tests, Froude Scaling is applied to match the dynamic similarity for the bomb model, and the ejector force is simulated by using small pneumatic cylinders. The results indicate that the test bomb model safely separates from the internal bay at the given test conditions and configurations. It is also observed that the effects of the flow velocity and ejector force application have greater impacts on the separation trajectories than those of angle of attack and flap deflection.

An Experimental Study on the Determination of Backlayering Distance in Tunnel Fires (터널 화재시 역기류의 위치 결정에 관한 실험적 연구)

  • 이성룡;유홍선
    • Tunnel and Underground Space
    • /
    • v.14 no.4
    • /
    • pp.269-274
    • /
    • 2004
  • In this study reduced-scale experiments were conducted to determine the backlayering distance in tunnel fires. The 1/20 scale experiments were carried out under the Froude scaling using ethanol square pool fire ranging from 8 to 1km in each side with total heat release rate from 2.47 to 12.30 ㎾. It has been found that ventilation velocity increases with aspect ratio(tunnel height/tunnel width). At L$\_$B/$\^$*/ <5 the ventilation velocity increases proportional to the backlayering distance from 0.25 power of the heat release rate. However at L$\_$B/$\^$*/ $\geq$5 the ventilation velocity varies as the 0.3 power of the heat release rate.