그라인딩 작업 중 발생하는 불티의 화재 예방에 관한 연구 (A Study on the Risk of Fire Caused by Sparks during Grinding Operation)

  • 김성은;이근출;박경진
    • 한국산업융합학회 논문집
    • /
    • 제26권5호
    • /
    • pp.751-756
    • /
    • 2023
  • In this study, We investigated a fire case and performed an experiment to prevent fire from sparks that is generated during grinding operation. Before conduct the test, confirmed that the generating mechanism of fire-flakes in working grinder and the fire experiment was conducted using commonly tools, flammable materials in industrial field. in result, It could be measured scattering distance, temperature, ignition possibility by type of combustible materials. Based on the results of this study, We are expected to be used as basic data for fire prevention in grinding Industry.

화목보일러 화재위험성에 관한 실험적 연구 (An Experimental Study on the Fire Risk of a Firewood Boiler)

  • 이성룡
    • 한국화재소방학회논문지
    • /
    • 제29권3호
    • /
    • pp.37-42
    • /
    • 2015
  • 본 연구에서는 농촌지역을 중심으로 대표적인 겨울철 난방기구인 화목보일러 화재위험성을 평가하였다. 화목보일러 연료투입구 주변 및 연통의 온도를 측정하였으며, 연통 내부에 축적되는 타르의 화재 위험성을 평가하였다. 연료 투입구개방 상태에서 전방의 온도를 측정한 결과 화목 투입구로부터 40 cm 이상 떨어진 영역에서는 온도가 약 $40^{\circ}C$ 이하를 유지하였다. 본 연구에서는 연료 투입구 외부로 비산되는 불티가 60 cm 이내의 범위에 비산되었다. 연통 내부에서는 온도가 $600^{\circ}C$ 이상까지 상승하였으며, 화목보일러 본체로부터 2 m 떨어진 위치의 연통 내부에서 온도가 $420^{\circ}C$ 이상 도달하였다. 연통 내부의 타르를 수거하여 발화온도를 측정한 결과 약 $398^{\circ}C$를 기록하였다. 화목보일러 본체 및 연통 표면에서 온도가 약 $300^{\circ}C$ 이상 도달하였으며 가연물이 접촉될 경우 착화되었다.

용접·용단 작업 중 사고 예방을 위한 제도 개선 연구 (A Study on the Improvement of System to Prevent Accidents during Welding and Melting Operations)

  • 한경수;조규선;김영세;김병직;박주영;박교식
    • 한국가스학회지
    • /
    • 제24권1호
    • /
    • pp.76-81
    • /
    • 2020
  • 최근 가연물이 있는 장소에서 용접·용단 작업 중 불꽃 비산 등으로 인한 화재·폭발사고가 빈발하고 있으며, 이러한 화재사고의 원인은 위험물 제거, 불꽃 비산방지 조치 등 기본적인 안전수칙 미준수가 대부분으로 산업안전보건법의 제도적인 보완이 필요하다. 본 연구에서는 국내 용접·용단 작업 등 화기작업에서의 화재·폭발 사고를 시스템적 관점에서 분석하고 그 결과를 반영하여 화재감시자 배치 확대, 화재위험작업의 사전승인, 화재예방 안전교육 강화 등 제도개선방안을 제안하였다.

잠재적 화재.폭발 위험 지역 작업용 녹전환형 중방식 코팅제의 특성에 관한 연구 (A Study on the Properties of the Heavy Duty Rust-Converting Agent used in the Potential Hazard Areas of Fire & Explosion)

  • 강영구
    • 한국안전학회지
    • /
    • 제13권3호
    • /
    • pp.102-111
    • /
    • 1998
  • This study was concerned with the development of a heavy duty rust-converting agent, the function of which is to form metal complex coatings, containing vinyl halide-acrylic terpolymer emulsion, defoamer, emulsifying agent, glass flakes, chelating agent such as gallotannic acid, gallic acid, and pyrogallic acid, and other additives. The resulted emulsion products(Sample No.1~No.5) were characterized through test either in the forms of emulsions, which include Viscosity, Penetration rate, Acidity and Film drying rate test, or in the forms of coated layer on rusty steel substrates by FT-IR, which include hardness, gloss, salt spray, adhesion and flame retardant test. The test results are as follows ; Penetration rate(0.1~0.4 mm/min), Solid content(70%), Acidity (pH 1.8~2.0), Specific gravity(1.30~1.35), Film drying rate(108min, RH 40% ; 150min, RH 80%), Gloss(83~92, incident angle $60^{\circ}$; 88~97, incident angle $85^{\circ}$), Pencil hardness(4H~5H), Adhesion (100/100), Salt spray test(>720Hr), LOI(%) value(38%), Vertical burning test(UL 94-v-l). According to the various performance of specimens show above, the evaluation of the availability of this heavy duty rust-converting agent can be concluded that all the samples(No.1~No.5) are capable of being used in the field of chemical plant and in the hazard areas of fire and explosion potential. It was observed that the properties of sample No.2, especially gloss and hardness, were much better than that of the other samples.