• Title/Summary/Keyword: fire protection standard

Search Result 176, Processing Time 0.023 seconds

A Study on the Refractory Performance Verification of the Thermal Insulators for AES Ducts and Piping (AES 계열 덕트·배관 단열재의 내화성능 검증에 관한 연구)

  • Kwang-Ho Ham;Jea-Chun Sa;Joo-Hwan Lee;Se-Hong Min
    • Journal of the Society of Disaster Information
    • /
    • v.20 no.2
    • /
    • pp.419-429
    • /
    • 2024
  • Purpose: To enhance the non-combustibility of fire protection piping insulation and improve the heat resistance of smoke extraction duct insulation, I plan to verify the suitability of AES insulation materials for these applications through performance testing. Method: The non-combustibility, heat resistance, and thermal insulation performance of AES insulation materials will be verified through various tests. Result: According to the 'Standards for Flame Retardancy and Fire Spread Prevention of Building Finishing Materials,' the results of non-combustibility and gas toxicity tests confirmed the non-combustible properties. The standard fire resistance tests verified the fire resistance performance. Additionally, the thermal insulation performance was confirmed through building insulation tests. Conclusion: As the performance tests on AES inorganic insulation materials have proven their noncombustibility, fire resistance, and thermal insulation performance, these materials are considered a viable alternative for improving fire spread prevention in buildings.

The Physical Properties of the Block Using Flame Resistant EPS Wastes (폐 난연성 EPS의 혼합조건에 따른 재생골재 블록의 물성에 관한 실험적 연구)

  • Cho, Kwang-Hyun;Kim, Ji-Hyun;Chung, Chul-Woo;Lee, Jae-Yong;Lee, Soo-Yong
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2013.11a
    • /
    • pp.152-153
    • /
    • 2013
  • Based on the Fire Service Act of mandatory provision, new buildings are strictly forced to use fire protection materials. Flame resistant EPS is one of those materials. Unlike conventional EPS that can be fused to make EPS ingot and be recycled for various purposes, flame resistant EPS waste cannot be recycled due to the presence of protective coating that is applied to increase the fire protection properties of EPS. A suitable alternative that can process large amount of flame resistant EPS wastes needs to be developed, and one of the possible alternative is to use them as construction materials. In this research, experiments were designed to observe whether the flame resistant EPS wastes can be utilized as partial replacements of fine aggregates in cement mortar. The replacement ratio of waste EPS was varied, and its effect on compressive strength and absorption capacity was investigated. According to the experimental results, both compressive strength and absorption capacity met the Korean Standard specification for cement bricks and blocks, indicating that flame resistant EPS wastes can be used for construction purposes.

  • PDF

A Study on the Survey of Each Country's Standards to Prevent Flashover of Housing Building (주거시설의 플래시오버 방지를 위한 각국의 내장재 기준 조사에 관한 연구)

  • Hun, Ye-Rim;Kim, Yoon-Seong;Lee, Byeong-Heun;Jin, Seung-Heun;Kwon, Young-Jin
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2021.11a
    • /
    • pp.44-45
    • /
    • 2021
  • In Korea, the risk of fire in buildings is increasing. Therefore, efforts are needed to reduce casualties and property damage. Accordingly, it is important to limit the flashover so that the fire inside the building does not expand to the outside. Flashover refers to the generation of upward airflow after the fire in the compartment, and when combustible gas accumulates in the upper part of the fire chamber and reaches about 500℃, explosive expansion combustion occurs inside the compartment. This can suppress flashover due to limitations on building interior materials. To this end, internal limitations are being implemented at home and abroad through standards related to internal materials. In this paper, we intend to secure basic data on domestic fire safety design by comparing domestic and foreign standards and reviewing the Japanese housing interior design manual.

  • PDF

Study of the Standard Testing Specifications for a Non-loading Performance Evaluation of Coating Material-sprayed Circular Steel Structures (뿜칠 피복 원형 철골구조의 비재하 내화성능 평가용 시험체 제안을 위한 연구)

  • Ok, Chi-Yeol;Kim, Jae-Jun
    • Fire Science and Engineering
    • /
    • v.30 no.3
    • /
    • pp.7-15
    • /
    • 2016
  • The cross-sectional shape factor is used worldwide to evaluate the scientific performance of fire-resistant structures. In South Korea, however, a system for applying a cross-sectional shape factor has not been arranged and circular or rectangular steel pipes are commonly used for large-scale steel frame buildings. On the other hand, coating material-spray steel beams and pillars that have received the certification of a fire-resistant structure from recognized organizations are mostly limited to a H-beam. A H-beam is granted a wide range of certifications without size limitations from a non-loading performance test with test standards based on the relevant provisions. Other types of steel pipe are to be certified for fireresistance according to shape. In this study, a cross-sectional shape factor was used to propose standard testing specifications for the application of coating material-sprayed circular and rectangular steel pipes, eventually to set the scope of certification for reasonable fire-resistant structures.

Performance Analysis of the the Single Alarm Detector in the Rooms of Single Houses by Computer Simulation (시뮬레이션을 통한 주거공간 단독경보형감지기의 성능 분석)

  • Lim, Geun-Joo;Park, Sang-Cheon;Baek, Eun-Sun
    • Fire Science and Engineering
    • /
    • v.34 no.4
    • /
    • pp.29-35
    • /
    • 2020
  • This study was conducted to examine the performance in the space for a single alarm type detector installed in a single house. Three types of houses were used, including two types of one-story and two-story houses. A computer simulation program was used to predict the sound pressure level in response to the occurrence of an alarm sound in a residential space. The characteristics of the sound source applied to the simulation were directly measured and used as input data. As a result of simulation, it was found that the sound pressure level in the kitchen and living room generally met the standard when the alarm sound of the detector occurred. However, the sound pressure level in the bedroom was predicted to be at least 20 dB (A) lower than the American Fire Protection Association standard of 75 dB (A). Therefore, a plan should be prepared to maintain a sufficient sound level in the bedroom space inside the house, and efforts will be needed to ensure safe evacuation in case of fire by establishing relevant standards.

Fire Resistance of U-shape Hybrid Composite Beam (신형상 U형 하이브리드 합성보의 내화성능에 관한 연구)

  • Kim, Sung Bae;Kim, Sang Seup;Ryu, Deog Su;Choi, Seng Kwan
    • Journal of Korean Society of Steel Construction
    • /
    • v.25 no.4
    • /
    • pp.379-388
    • /
    • 2013
  • This paper aims to experimentally investigate the fire resistance of U-shaped hybrid composite beams protected by spay and paint insulations. Subjected to two and three hours of the Standard ISO fire, the flexural performance of 4.4m beams with/without imposed loadings was examined with respect to failure criteria such as deflection and deflection rate of the mid-span and temperatures measured in the steel section. The results demonstrated that the proposed configuration of the composite beam is able to achieve a very competitive 3-hour fire resistance rating in economical aspects.

A Study on the Recognition of Fire Construction Surveillance System : Focused on the Stakeholders (소방공사감리제도의 인식에 관한 연구 : 이해당사자를 중심으로)

  • Lee, Ranny;Jeong, Kyeon-Sik;Kong, Ha-Sung
    • Journal of the Korea Safety Management & Science
    • /
    • v.16 no.3
    • /
    • pp.133-143
    • /
    • 2014
  • The purpose of this article is to search stakeholders' recognition related to Fire Construction Surveillance system; a client(order), fire fighting officer, supervision company, construction company, design company, other. The paper provides 4 important things. Firstly, a client(order) suggested the lowest recognition in the needs about the need of separation order, that of contract for any construction work limited registered companies, and that of standard price for engineering.. Secondly, the design company is lowest recognition in guidance and control participating in construction-design phase. Thirdly, the design company is lowest in adjustment about manpower-allocation according to allocation criteria of technical manpower. Fourthly, a client(order) and supervision company are relatively lower than other stakeholder in necessity on special education and training system for auditor in fire protection construction. Almost all related matters are related to more or less stakeholders' interest.

Time-Temperature Curve of road tunnel for fire (도로터널 내 화재에 따른 시간-온도 가열곡선 도출)

  • Choi, Min-Jung;Jang, Chang-Il;Lee, Sang-Woo;Kim, Joon-Mo;Won, Jong-Pil
    • Proceedings of the Korea Concrete Institute Conference
    • /
    • 2008.04a
    • /
    • pp.713-716
    • /
    • 2008
  • This study is performed to propose a standard to evaluate fire protection assessment for concrete structures during a fire on road tunnel. Recently, a number of road tunnels have been rapidly increased and fire risk also multiplyed according to extend tunnel length, due to natural features and environmentally-friendly road construction in domestic. But we have not yet been prescribed appropriate time-temperature curve for tunnel fire. Therefore we presented fire design model and investigated time-temperature curve proposed by a foreign country considering traffic, a kinds of vehicles which are a basis of heat rate.

  • PDF

Analysis of Heat Characteristics for Fault Power Utility (전기설비 사고의 열적 특성 분석)

  • 김기화
    • Fire Science and Engineering
    • /
    • v.11 no.4
    • /
    • pp.25-31
    • /
    • 1997
  • In this study, EMTP(Electromagnetic Transients Program) which is one of the most well-known computer simulation methods is used to collect the data for a power plant fault. EMTP is the program for an interpretation of the phenomena of electric transients, and is designed to manifest the data of the electric current and voltage etc. at the time of a power plant fault. By EMTP, I analyze the properties of the heat energy which are transferred from the electrics when a power plant fault brings out. In terms of the results of this study, it is able to measure the heat energy at a power plant fault (power transformer) and to be acquired of the related data. And moreover, these data are expected to be used as a standard for the protection of the fire owing to a high voltage power transformer fault.

  • PDF

A Study on the Fire Resistance Performance Concerning Types of Fire Protection Method and Load Ratio of High Strength Concrete Column Using The Wire Rope (와이어로프를 적용한 고강도 철근콘크리트 기둥의 내화공법 및 하중비에 따른 내화성능에 관한 연구)

  • Cho, Bum-Yean;Yeo, In-Hwan;Kim, Heung-Youl;Kim, Hyung-Jun;Kwon, In-Kyu
    • Fire Science and Engineering
    • /
    • v.26 no.6
    • /
    • pp.64-71
    • /
    • 2012
  • The fire resistance test has been conducted under the standard fire & loading conditions to evaluate fire resistance performance, according to applying to methods of the lateral confinement reinforcement by prestressed Wire Rope and fire resistance reinforcement by Fiber-Cocktail and load ratio for high strength concrete column. The test result, for 60 MPa high-strength concrete column, It was indicated that applying to the wire rope has improved axial ductility in the fire condition, and fire resistance performance has been enhanced by more than 23 %. In addition to this, in case of applying the wire rope to 60 MPa high-strength concrete column, load can be judged that about 70 % of designed load is appropriate. If the Wire Rope and Fiber-Cocktail is applied to 100 MPa high-strength concrete column, It was shown that the fire resistance performance was enhanced by 4 times as much as applying only hoops.